29
3.2.8 Reading Adjust Menu
For Temperature Reading
only, not Process
Figure 3.7 Flow Chart for Reading Adjust Menu
ENTER READING ADJUST MENU:
Press
a
Press
d
Press
a
1)
Press
a
, if necessary until
CNFG
prompt appears.
2)
Display advances to
INPT
Input Menu.
3)
Press
a
,if necessary, until display advances to
R.ADJ
Reading Adjust Menu.
READING ADJUST VALUE SUBMENU:
Press
d
Press
b
&
c
Press
d
4)
Display flashes first digit of previous Reading Adjust value.
5)
Press
b
and
c
buttons to enter a new Reading Adjust value
(-1999 to 9999).
6)
Display shows
STRD
stored message momentarily and then
advances to
SP.DV
Setpoint Deviation Menu.
Reading Offset Adjust
allows the user to fine tune a minor error of the
ransducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ±R.ADJ).
Reading Adjust value is adjustable between -1999 to 9999.
3.2.9 Setpoint Deviation Menu / Field Calibration
Figure 3.8 Flow Chart for Setpoint Deviation Menu / Field Calibration
ENTER SETPOINT DEVIATION MENU:
Press
a
Press
d
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
2)
Display advances to
INPT
Input Menu.
3)
Press
a
, if necessary, until Display advances to
SP.DV
Setpoint Deviation Menu.