23
3.2.5 Reading Configuration Menu (continued)
Conversion number is a coefficient of conversion between input values
and real full display range (10000 counts). See
Table 3.2
below for
proper conversion number.
Table 3.2 Conversion Table
RANGE
CONVERSION NUMBER
100 mV
10000 / (100 x 1) = 100
1 V
10000 / (1000 x 1) = 10
10 V
10000 / (1000 x 10) = 1
0 to 20 mA
10000 / (20 x 1) = 500
Example =
0 - 1 V = 0 - 100.0
In 1 = 0
Rd 1 = 0
Inp 2 = 9999
Rd 2 = 100.0