background image

2

1.2  Safety Considerations

This device is marked with the international caution symbol. It is 

important to read this manual before installing or commissioning this 

device as it contains important information relating to Safety and 

EMC (Electromagnetic Compatibility).
This device is a panel mount device protected in accordance with  

EN 61010-1:2001, electrical safety requirements for electrical 

equipment for measurement, control and laboratory. Installation of this 

device should be done by qualified personnel. In order to ensure safe 

operation, the following instructions should be followed.
This device has no power-on switch. An external switch or circuit-

breaker shall be included in the building installation as a disconnecting 

device.  It shall be marked to indicate this function, and it shall be in 

close proximity to the equipment within easy reach of the operator.  

The switch or circuit-breaker  shall meet the relevant requirements of 

IEC 947–1 and IEC 947-3 (International Electrotechnical Commission). 

The switch shall not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being 

drawn from the main supply in case of a fault in the equipment, an 

overcurrent protection device shall be installed.
•   Do not exceed voltage rating on the label located on the top of

   the device housing.

•   Always disconnect power before changing signal and power

   connections.

•   Do not use this device on a work bench without its case for

   safety reasons.

•  Do not operate this device in flammable or explosive atmospheres.

•   Unit mounting should allow for adequate ventilation to ensure

   device does not exceed operating temperature rating.

•   Use electrical wires with adequate size to handle mechanical

   strain and power requirements. Install without exposing bare wire

   outside the connector to minimize electrical shock hazards.

EMC Considerations

•   Whenever EMC is an issue, always use shielded cables.

•   Never run signal and power wires in the same conduit.

•   Use signal wire connections with twisted-pair cables.

•   Install Ferrite Bead(s) on signal wires close to the device if

   EMC problems persist.

Failure to follow all instructions and warnings may result in injury!

Содержание i16-AL

Страница 1: ...www newportUS com manuals Temperature Process Limit Alarm Controller i8 AL i16 AL i32 AL Operator s Manual...

Страница 2: ...ucts are not designed for use in and should not be used for patient connected applications TRADEMARK NOTICE NEWPORT NEWPORT newportUS com and the Meter Bezel Design are trademarks of NEWPORT Electroni...

Страница 3: ...iguration Mode 12 3 1 Introduction 12 Turning your device On for the First Time Buttons Functions in Configuration Mode 3 2 Menu Configuration 13 3 2 1 ID Number 14 3 2 2 Setpoints 15 3 2 3 Configurat...

Страница 4: ...ow Chart for ID and Setpoints 13 Figure 3 2 Flow Chart for Configuration Menu 16 Figure 3 3 Flow Chart for Input Type Menu 17 Figure 3 4 Flow Chart for Reading Configuration 21 Figure 3 5 Flow Chart f...

Страница 5: ...ications accepting 10 different thermocouple types 18 RTD combinations or 4 process voltage current inputs and providing 2 relay alarm outputs and a large multi color programmable display Easily confi...

Страница 6: ...echnical Commission The switch shall not be incorporated in the main supply cord Furthermore to provide protection against excessive energy being drawn from the main supply in case of a fault in the e...

Страница 7: ...ent is necessary Customer Service If you need assistance please call the nearest Customer Service Department listed in this manual Manuals The latest Operation Manual is available from the website lis...

Страница 8: ...tpoint 2 Alarm 2 indicator C C unit indicator F F unit indicator a Changes display to Configuration Mode and advances through menu items b Used in Program Mode and Peak Recall c Used in Program Mode a...

Страница 9: ...4 3 2 1 L N OUTPUTS INPUTS L N OUTPUTS Figure 2 2 Rear Panel Figure 2 3 Rear Panel Input Connector Labels Table 2 2 Rear Panel Connector POWER AC DC Power Connector All models INPUT Input Connector Al...

Страница 10: ...Agency Approved DC or AC source with the same Overvoltage Category and pollution degree as the standard AC unit 90 to 240 Vac The Safety European Standard EN61010 1 for measurement control and labora...

Страница 11: ...ect Thermocouple and Thermocouple Type in the Input Type menu see Part 3 Figure 2 5 Thermocouple Wiring Hookup Table 2 4 TC Wire Color Chart Type Input Connector Jacket External Insulation Terminal 1...

Страница 12: ...easures the RTD plus upper and lower lead drop voltage and the subtracts twice the measured drop in the lower supply current lead producing excellent lead resistance cancellation for balanced measurem...

Страница 13: ...the wiring hookup for Process Voltage 0 100 mV 0 1 V 0 10 V Figure 2 8 a Process Voltage b Process Voltage Wiring Wiring Hookup with Hookup without Sensor Sensor Excitation Excitation RL Voltage limit...

Страница 14: ...iring Outputs This device has two factory installed outputs The SPDT Mechanical Relay Connection is shown below Figure 2 9 Mechanical Relay Output Wiring Hookup Use copper conductors only for power co...

Страница 15: ...igate through the menu options and configure the device Part 3 of this manual will explain the Menu Configuration Mode For your device to operate properly the user must first program or configure the...

Страница 16: ...evel Menu item Press this button twice to reset the device to the Run Mode When a numerical value is flashing except set point value press c to scroll digits from left to right allowing the user to se...

Страница 17: ...13 3 2 Menu Configuration Figure 3 1 Flow Chart for ID and Set Points Menu...

Страница 18: ...he instrument will return to the Run Mode To change ID Code see ID Menu in the Configuration section ENTERING YOUR NON DEFAULT SET POINT ID SECURITY ID NUMBER Press a Press a Press a Press d Press b c...

Страница 19: ...value 5 Display shows STRD stored message momentarily and then advance to SP2 only if a change was made otherwise press a to advance to SP2 Setpoint 2 Menu SETPOINT 2 Press d Press b c 6 Display show...

Страница 20: ...ONFIGURATION MENU Press a Press d Press b c 1 Press a if necessary until CNFG prompt appears 2 Display advances to INPT Input Menu 3 Press and release a to scroll through all available menus of Config...

Страница 21: ...Scroll through the available selection to T flashing 5 Display shows STRD stored message momentarily and then T not flashing 6 Display flashes previous thermocouple type selection i e J see below for...

Страница 22: ...type selection i e 392 2 see below for RTD types selection 7 Scroll through the available RTD types to the selection of your choice 8 Display shows STRD stored message momentarily and then advances t...

Страница 23: ...ing 5 Display shows STRD stored message momentarily and then PROC not flashing 6 Display flashes previous Process type selection i e 0 10 see below for Process types selection 7 Scroll through the ava...

Страница 24: ...ding Configuration Menu 4 Display advances to DEC Decimal Point DECIMAL POINT SUBMENU Press d Press b Press d 5 Display flashes previous selection for Decimal location 6 Scroll though the available se...

Страница 25: ...evious selection for Filter Constant 12 Scroll though the available selections 0001 0002 0004 0008 0016 0032 0064 0128 13 Display shows STRD stored message momentarily only if change were made otherwi...

Страница 26: ...nput 1 submenu 15 Display shows Input 1 value with first digit flashing 16 Use b and c buttons to enter IN1 value The IN1 value min input value conversion number Disregard the position of the decimal...

Страница 27: ...ut values and real full display range 10000 counts See Table 3 2 below for proper conversion number Table 3 2 Conversion Table RANGE CONVERSION NUMBER 100 mV 10000 100 x 1 100 1 V 10000 1000 x 1 10 10...

Страница 28: ...ss a Press d Press a Press d 1 Press a if necessary until CNFG prompt appears 2 Display advances to INPT Input Menu 3 Press a if necessary until display advances to ALR1 Alarm 1 Menu 4 Display advance...

Страница 29: ...rocess being monitored does not change often then Absolute Mode is recommended Deviation Mode allows changes to Setpoint 1 to be made automatically to Alarm 1 Deviation Mode is typically the ideal mod...

Страница 30: ...ion triggered when the process variable is less than the Alarm Low Value or above the Hi Value Band Alarm 1 condition triggered when the process variable is above or below the band set around Setpoint...

Страница 31: ...m is not active while the process value is approaching Setpoint 1 ALARM 1 LOW VALUE SUBMENU Press d Press b c Press d 15 Display flashes first digit of previous value Use b and c to enter new value 16...

Страница 32: ...BLE DISABLE SUBMENU Press b Press d 5 Display flashes previous selection Press b until ENBL displays to use Alarm 2 6 Display shows STRD stored message momentarily and then advances to ABSo only if it...

Страница 33: ...lue 1999 to 9999 6 Display shows STRD stored message momentarily and then advances to SP DV Setpoint Deviation Menu Reading Offset Adjust allows the user to fine tune a minor error of the ransducer ho...

Страница 34: ...ving SP1 to 300 the absolute value of SP2 becomes 320 THERMOCOUPLE FIELD CALIBRATION SUBMENU CAUTION Do not perform the following steps until you fully understand this entire section RTD and Process a...

Страница 35: ...ces to ____ with first under score flashing Press b c 5 Press b and c to enter your 4 digit ID Code number Press d 6 Display advances to CH ID Change ID Code Submenu If entered ID Code is incorrect di...

Страница 36: ...urity Level is Enabled and the user attempts to enter the Main Menu they will be prompted for an ID Code The ID Code should be correct to enter the instrument Menu item SETPOINT ID SECURITY LEVEL SUBM...

Страница 37: ...previous selection for Normal Color Press b 6 Scroll through the available selections GRN RED or AMBR Press d 7 Display shows STRD stored message momentarily and then advances to 1 CLR only if it was...

Страница 38: ...s should be set in such a way that Alarm 1 value is always on the top of Alarm 2 value otherwise value of Alarm 1 will overwrite value of Alarm 2 and Display Color would not change when Alarm 2 is tri...

Страница 39: ...larm 2 is designed to monitor the Process Value around the Setpoint 2 Example 4 Setpoint 1 200 Setpoint 2 200 Alarm 1 Setup Deviation Band ALR H 20 Alarm 2 Setup Deviation Hi Low ALR H 10 ALR L 5 Colo...

Страница 40: ...R S B C N L J DIN Thermocouple Lead Resistance 100 ohm max RTD Input ITS 68 100 500 1000 Pt sensor 2 3 or 4 wire 0 00385 or 0 00392 curve Voltage Input 0 to 100 mV 0 to 1 V 0 to 10 Vdc Input Impedance...

Страница 41: ...Delay UL 248 14 listed 100 mA 250 V 400 mA 250 V Low Voltage Power Option Time Lag IEC 127 3 recognized 100 mA 250 V 400 mA 250 V Low Voltage Power Option Environmental Conditions 0 to 55 C 32 to 131...

Страница 42: ...104 F 1 8 F 104 to 3250 F 0 9 F S Pt 10 Rh Pt 50 to 100 C 1 0 C 100 to 1768 C 0 5 C 58 to 212 F 1 8 F 212 to 3214 F 0 9 F B 30 Rh Pt 6 Rh Pt 200 to 640 C 1 0 C 640 to 1820 C 0 5 C 212 to 1184 F 1 8 F...

Страница 43: ...ive ACTV Below BELO Alarm 1 At Power On A P ON Enable ENBL Alarm 1 only Alarm 1 Low ALR L 32 00 Alarm 1 High ALR H 000 0 Alarm 2 Alarm 2 ALR2 Disable DSBL Absolute Deviation ABSO DEV Absolute ABSO Lat...

Страница 44: ...Neutral working voltage is 50Vac dc This unit should not be used in Measurement Categories II III IV Transients Overvoltage Surge 1 2 50uS pulse Input Power 2500V Input Power 1500V Low Voltage dc Powe...

Страница 45: ...NOTES...

Страница 46: ...NOTES...

Страница 47: ...erwise shall not exceed the purchase price of the component upon which liability is based In no event shall NEWPORT be liable for consequential incidental or special damages CONDITIONS Equipment sold...

Страница 48: ...M5290 N 0613...

Отзывы: