[ENG] 8.1 [DKSF 48.4 IU] Configuring Relay Management Modes
Management modes of built-in relays are configured at the page «
» of a device web interface:
AC OUTLETS
This page allows to control eight output channels (relays) of a device power supply. A channel may be switched off for a short time, set to the mode «M
», «
», «
», «
», «
», «
».
anual Off
Manual On
Schedule
Watchdog
SWatchdog
Logic Output
Relay Control – is a current status of a relay. It is possible to specify the next values:
Manual Off – a relay is constantly switched off;
Manual On – a relay is constantly switched on;
Watchdog – a relay is controlled by the module «
»;
Watchdog
Schedule – a relay is controlled by the module «
»;
Schedule
SWatchdog – a relay is controlled by both modules «
» and «
» simultaneously. The module «
» switches a
Watchdog
Schedule
Schedule
relay on and off. The module «
» checks the operability of a connected device depending on the module «
». If the module «
Watchdog
Schedule
» notices a failure in a device operation (no response to ICMP request), a relay changes its status to the opposite one for a short time;
Watchdog
Logic – a relay is used as a logic output
Switch Off for Short Period (15s) – when clicking the button «
», a corresponding relay will be switched off for 15 seconds.
Reset
Relay State – is a current status of a relay of each of eight sockets. Possible variants are: «
», «
».
Off
On
Outlet is Powered – is an availability of the voltage for every socket out of eight ones. Possible variants: «
», «
».
Yes
No
A status of a relay and voltage at sockets are updated automatically when a relay status is changed or a voltage is present with no need to reload the
entire page.
Memo – is a field for viewing or changing a brief description of a relay. A value in this field will be used in SYSLOG notifications, records at the page «
», as well as included into SMS, E-mail notifications, E-mail reports about a status of sensors and indicated in headings of pop-up dialogs and
LOG
module configuration «Watchdog» and «Schedule». Maximum size is 30 characters.
: empty line.
On default
After setting up all necessary parameters click the button «
».
Apply changes