[ENG] 10.3. [DKSF 48.4 IU] Configuring Thermostat
To configure a thermostat, there is a need to go to the page «
» of a device web interface:
LOGIC
In the section «
» parameters of a thermostat are configured.
Thermo(Hygro)stat
A thermostat is used to support a constant temperature. Besides a programmed thermostat, there is a need to set a minimum of two rules: one rule for
switching a heater or a cooler on and another one for switching it off. It is possible to configure no more than two channels of a thermostat – «TSTAT 1
», «
». A corresponding thermostat is chosen as a source of information (input) in logic rules, which control a heater or a cooler.
TSTAT 2
Sensor – is a number of a temperature sensor, with which a thermostat works. It is possible to plug up to 8 temperature sensors to a device with an
individual number from 1 to 8.
: 1
On default
Current value, deg.C or % rel.hum. is readings of a sensor in a current moment of time.
–
Threshold, deg
.С or % rel.hum. – is a temperature, which will be maintained by a thermostat (in whole degrees of Celsius, a value can be below zero).
O
: 20
n default
Hysteresis, 1..8 deg.С or % rel.hum. – a hysteresis sets a «dead zone» near a specified temperature, within the limits of which a thermostat does not
respond to temperature fluctuations. This function allows to avoid frequent accidental switching of a heater (cooler) caused by natural spontaneous
fluctuations of a temperature, measured by a temperature sensor. If a current status of a thermostat is «
», then a threshold for
above (threshold
)
M
switching a status is a specified temperature minus a hysteresis value. And vice versa, if a current status is «
», then a switching
below (threshold
)
M
threshold is a specified temperature plus a hysteresis value. As soon as a temperature reaches a threshold value increasing or decreasing (taking
hysteresis into account), and thus leaves the thresholds of a «corridor», a status of a thermostat is changed to the opposite one.
: 2
On default
Status – is a status of thermostat channels «
», «
». It may take the next values: «
», «
», «
TSTAT 1
TSTAT 2
sensor failed
above (threshold M)
below (thresh
».
old
)
M
After setting up the values, there is a need to click the button «
.
Apply changes»
After configuring a thermo(hygro)stat, there is a need to configure a rule in the module «
». It is possible to learn how to do this from the section «
Logic
».
10.2. [DKSF 48.8 IU] How to Use the Module «Logic»?