[ENG] 5.4. [DKSF 48.4 IU] Browsing Readings and Configuring Parameters of a Humidity Sensor in a Web
Interface
To browse readings and a configuration of humidity sensor parameters, there is a need to go to the page «
» of a device web interface:
HUMIDITY
where:
Sensor status – determines a sensor status in a current moment of time. Possible variants are: «
», «
», «
sensor failed
within a safe range
below a safe range
», «
»;
above a safe range
Relative Humidity – shows readings of a sensor, which measures a relative humidity in %;
Temperature – shows readings of a temperature sensor, embedded into a humidity sensor, in
°C;
Dew Point – is a dew point temperature, which is calculated from readings of a humidity sensor and a temperature, in
°C;
Top Margin of Humidity Safe Range – is a humidity value, exceeding which a sensor switches to a status «
». Hysteresis is 1
above a safe range
±
percentage point.
: 85
On default
Bottom Margin of Humidity Safe Range – is a humidity value dropping below which a sensor switches to a status «
». Hysteresis is
below a safe range
±
1 percentage point.
: 5
On default