[8PWR] Sensors Plugin
Sensors of Dry Contact Type
Dry contact sensors are: door opening sensors, buttons and other sensors, which mechanism is in opening/closing a conductor. A sensor is connected
with two wires to an IO line of a device according to the table (an order of plugging wires does not matter).
Sensor Flex
Netping 8/PWRv3/SMS Terminal
First wire
– 1
One of IO lines
/2/3/4
Second wire
G
A sensor is packaged with an inseparable cable, with connectors on the ends. A cable length can be increased with the help of
flat cable extenders of
sensor, which are sequentially plugged one into another. Or it can be done independently with the help of any wire with a minimum cross section
RC-4
of 0,4 mm . Maximum allowable length of a flat cable is 100 m.
2
Temperature Sensors
TS- and WT- temperature sensors are plugged in by a four-wire line according to the table.
Sensor Flex
Netping 8/PWRv3/SMS Terminal
Labelled wire (red).
C
Second wire after a labelled one
D
Third wire after a labelled one
+
Fourth wire after a labelled one
G
It is possible to plug up to 8 temperature sensors to a device – four TS-sensors and four WT-sensors. Sensors are connected in a parallel to the same
terminals.
Leakage Sensors
A leakage sensor is connected by a four-wire line according to the table.
Sensor Flex
Netping 8/PWRv3/SMS Terminal
Green.
One of IO lines – 1/2/3/4
Yellow (White)
G
Red
+
Black
G
!
Important Sensors of a dry contact type, a 220 V occurrence sensor, a leakage sensor and others are plugged to IO lines of a device. You can
plug any four sensors out of this set.
!
Important A corresponding IO line should be set to an input mode in settings of a device.
Important! It is prohibited to plug sensors with the same numbers to a device.
Important! Sensors of a dry contact type, a 220 V occurrence sensor, a leakage sensor and others are plugged to IO lines of a device. You can
plug any four sensors out of this set.