Copyright © NetPing east Co., Ltd E-mail:
Phone:+886-2-23121582
.1.3.6.1.4.1.25728.8800.2.3.0
Integer
A sensor status:
0 – failure or disconnection of a sensor
1 – temperature is below normal
2 – temperature is normal
3 – temperature is above normal
.1.3.6.1.4.1.25728.8800.2.4.0
Integer
Lower limit of a safe range, °C.
.1.3.6.1.4.1.25728.8800.2.5.0
Integer
Upper limit of a safe range, °C.
.1.3.6.1.4.1.25728.8800.2.6.0
DisplayString
Memo (a text description of an installation place of a temperature sensor, coding win1251).
SNMP TRAP when Changing a Status of a Smoke Sensor
npSmokeTrap Identification
SNMP v1 enterprise
.1.3.6.1.4.1.25728.8200.2
SNMP v1 generic-trap
enterpriseSpecific(6)
SNMP v1 specific-trap
1
SNMP v2 snmpTrapOID
.1.3.6.1.4.1.25728.8200.2.0.1
Variables in npSmokeTrap (varbind list)
OID
Data Type
Description
.1.3.6.1.4.1.25728.8200.2.1.0
Integer
A number of a smoke sensor (1..4), changing a status of which caused sending a TRAP notification.
.1.3.6.1.4.1.25728.8200.2.2.0
Integer
Loop status:
0 – Norm
1 – Alert
4 – Disabled
5 – Failure
.1.3.6.1.4.1.25728.8200.2.6.0
DisplayString
Memo (a text description of an installation place of a temperature sensor,coding win1251).
SNMP TRAP when Changing a Status of a Humidity Sensor
npRelHumTrap Identification
SNMP v1 enterprise
.1.3.6.1.4.1.25728.8400.9
SNMP v1 generic-trap
enterpriseSpecific(6)
SNMP v1 specific-trap
1
SNMP v2 snmpTrapOID
.1.3.6.1.4.1.25728.8400.9.0.1
Variables in npRelHumTrap (varbind list)
OID
Data Type
Description