L
NAPCO Security Systems
X
GEM-P1632 Programming Instructions
!
Page 33
Default depends on Easy Menu Question “
# OF ZNS IN AREA 1 ENTER # ZONES
” and “
EZ ZONE DOUBLING? Y/N
”. For example, if 32 zones are used and Zone Doubling
is
not
enabled, then all 6 groups will be automatically enabled. If 32 zones are used and Zone Doubling is enabled, then only groups 1-4 will be automatically enabled.
NOTE:
If “Zone Doubling” (Address 0721) is
not
enabled, then Zones 1-8 are included in the control panel and Zones 9-32 (Groups
1-6) are EZM Zones. If “Zone Doubling” is enabled, then Zones 1-16 are included in the control panel and Zones 17-32 (Groups 1-4)
are EZM Zones (and Groups 5 and 6 must not be used).
EZM GROUP OPTIONS:
Up to 6 Groups of 4 Zones each may be programmed
depending on the number of zones used and which EZM modules are connected.
Each group represents 4 zones.
!
1. Select EZM type from the table shown.
!
2. Enter in corresponding address locations above (right digit only).
NOTE:
Dark shaded data value box shows option not available.
!
3. Press
U
or
D
to save.
AREA ARMING OPTIONS (ADDRESS 0743 & 0744)
PRIORITY AREA ARMING:
!
1. Select option from the table shown.
!
2. Enter in corresponding right digit address location (left
digit is not used).
NOTE:
Dark shaded data value box shows option not available.
!
3. Press
U
or
D
to save.
EZM
Group &
A
rea
A
rming Optio
n
s
EZM GROUP OPTIONS (ADDRESS 0737-0742)
EZM Group 1
LEFT
RIGHT
blank
ADDRESS 0737
EZM Group 2
LEFT
RIGHT
blank
ADDRESS 0738
EZM Group 3
LEFT
RIGHT
blank
ADDRESS 0739
EZM Group 4
LEFT
RIGHT
blank
ADDRESS 0740
EZM Group 5
LEFT
RIGHT
blank
ADDRESS 0741
EZM Group 6
LEFT
RIGHT
blank
ADDRESS 0742
DATA
ENTRIES
OPTION
RIGHT
blank (•)
Not used
(No EZM
present)
1
4-Zone EZM
EZM TYPE
PRIORITY ARMING/AREA 1
OPTION
LEFT
RIGHT
blank (•)
blank (•) Not Used
blank (•)
1
Enabled
DATA ENTRIES
PRIORITY ARMING/AREA 2
OPTION
LEFT
RIGHT
blank (•)
blank (•) Not Used
blank (•)
1
Enabled
DATA ENTRIES
Priority
ADDRESS 0743
Arming
LEFT
RIGHT
Area 1
blank (•)
[Default = blank (•) blank (•)]
Priority
ADDRESS 0744
Arming
LEFT
RIGHT
Area 2
blank (•)
[Default = blank (•) blank (•)]
EZM
GROUP NORMAL DOUBLED
1
9-12
17-20
2
13-16
21-24
3
17-20
25-28
4
21-24
29-32
5
25-28
6
29-32
ZONES COVERED