  GEM-P1632 Programming Instructions 

L

 NAPCO Security Systems 

!

 

Page 18

 

Key Fob Transmitters 

(Press 

R

 

to set cursor). 

Keyfobs can be programmed as “Arm/Disarm” devices (refer to WI752).  
For each Key Fob Transmitter, enter: 

!

The Key Fob Transmitter number (01–08). 

!

Area number to which transmitter is assigned (1 or 2); enter 0 to disable keyfob. 

!

The 6-digit RF ID # printed on the transmitter (enter all numbers and/or letters, including 

leading “0”s, if any). 

!

1-digit checksum number printed on the transmitter (enter all numbers and/or letters, including leading “0”s, if any). 

!

Aux-1 Option (see key fob aux 1 & aux 2 options). 

!

Aux-2 Option (see key fob aux 1 & aux 2 options). 

Press 

U

 to save.  Press the NEXT/YES button to proceed. 

 

Note:

  If the Key Fob is converted for Two Button “Emergency Use” (by cutting an internal jumper), 

both top or bottom buttons must be depressed to activate an alarm.  In this case, the Aux-1 and Aux-
2 cannot be programmed.   
 

Key Fob Transmitters as Zone Input Devices 

(refer to display above: press the PRIOR/NO button 

to go backwards). 

Each of the 4 key fob buttons can be assigned to a zone.  For example, On button = point 1; Off 
button = point 2; A1 = point 3; A2 = point 4.  Up to 32 key fobs (using 1 button) or 16 key fobs (using 
2 buttons) or 8 key fobs (using all 4 buttons) or any combination up to a maximum of 32 controlled 
zones can be assigned, providing multiple wireless panic buttons on a system, each reporting to the 
Central Station or a pager and/or annunciating on a keypad the key fob zone number with 

description/location.  

To assign a key fob to a zone:  

program the key fob as you would a transmitter, entering the key fob's ID code, 

check sum and point number at the appropriate zone.  The “Quick Method” is not allowed.  The zone may be hardwired to a sensor as 
well as assigned to a key fob (either one will activate the zone alarm output).  

NOTE: 

 If assigning a key fob to a zone, the “ON/OFF” 

buttons on the key fob will no longer arm/disarm the system. The key fob is converted to a “panic only” device.  

 

Dealer Code 

Directly enter the Dealer Code, including leading zeros. Use the 

1

 through 

9

 buttons.  

NOTE:

  Press 

0

 for a zero.  Press 

U

 to save.   

Re-enter the Dealer Code to verify the previous code.  Press 

U

 to save.  Press the NEXT/YES but-

ton to proceed.  

NOTE:

  The Dealer Code can be two or more digits (up to 6 digits). 

 

 
 

 
CLEAR PROGRAM:

  Should it be necessary to create a new custom default program, (a) from the Dealer Program Mode, press 

C

 to enter the Address Program Mode; (b) access Location 1197 (Clear Program) or 1198 (Cold Start); (c) press 

U

 and then (d) 

press 

C

 to exit the Dealer Program Mode.  A System Trouble Condition will occur.  Press 

C

 to silence the keypad. 

NOTE: Key fobs 1-8 report openings and 
closings as Users 25-32. 

 

DATA 

ENTRY 

AUX 1/AUX 2 

OPTIONS 

None 

Relay Group 1 Toggle 

Relay Group 2 Toggle 

Panic 

Auxiliary 

Instant 

PGM2 Output Toggle 

Access on PGM2 

Output 

Arm Stay 

Interior Button 

GEM-RP3DGTL/GEM-K3

DGTL A

N

GEM-RP4RFC/GEM

-K4RF  Ea

s

y Me

nu Dr

iv

en Pr

ogr

am 

Mode

 

 

 

29 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

KEY FOB ZONE ASSIGNMENT: 

 Key fobs can also be assigned to zones to allow multiple wireless panic buttons on one alarm 

system, each reporting to a central station, a pager or having a description on the keypad that describes the person holding the key 
fob, the location where the person holding the key fob is stationed, or the special purpose of the key fob button being depressed.  

See the next page on key fob Zone Assignment. 

(Direct Entry) 

 

33 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

rE 

ZONE DESCRIPTIONS: 

GEM-K3DGTL cannot be used to enter

 

Zone Descriptions. To enter Zone Descriptions, you must use the 

GEM-K1CA 

Keypad or the Napco Quickloader Software. 

DATE ENTRY: 

GEM-K3DGTL cannot be used to enter

 

the date. To enter Date, you must use the 

GEM-K1CA Keypad (Version 5 or later) or the 

Napco Quickloader Software. 

TIME ENTRY: 

GEM-K3DGTL cannot be used to enter

 

the time. To enter Time, you must use the 

GEM-K1CA Keypad (Version 5 or later) or the 

Napco Quickloader Software. 

EXIT DEALER PROGRAM MODE:

  This completes the custom default program.  Press 

C

 to enter the Direct Address Program 

Mode for further programming or press 

C

 once again to end all programming and resume normal keypad operation. 

Содержание Gemini GEM-P1632

Страница 1: ...p 5 Dealer Code Quick Start for GEM K3DGTL 1 Refer to the wiring diagram connect Siren Aux Power PGM Output Remote Bus Earth Ground Zone and Tele phone Wiring NOTE See Installation Instructions WI808...

Страница 2: ...27 All references to 0720 Bit 6 Enable PGM2 Chirp on Keyfob Arming name changed to Chirp Output on Keyfob Arm Disarm Page 27 All references to 0722 Bit 0 Automatic Interior Bypass name changed to Aut...

Страница 3: ...tral Station Receiver 1 Account Number 16 Central Station Receiver 1 Format 16 Enter User Codes 16 RF Transmitter Points 17 Key Fob Transmitters 18 Key Fob Transmitters as Zone Input Devices 18 Dealer...

Страница 4: ...amming The Direct Address Program Mode is an extension of the Dealer Program Mode wherein data is entered at the keypad by specific location This mode is accessed from the Easy Menu Driven Program Mod...

Страница 5: ...Dealer Program Mode when finished Dealer Code Default 456789 Number of Zones in Area 1 Panel Zone Doubling Fire Zones in Area 1 2 Wire Fire Zones in Area 1 Local or Central Station Reporting System Ex...

Страница 6: ...ton Fire Zones in Area 1 Appears for New Panel Only Enter the zone number of any zones which are to be used as Fire Zones both 2 wire 4 wire or wireless Valid entries are from 01 to 32 Directly enter...

Страница 7: ...e a distinct pulsating tone when zone is faulted Exit Entry2 Zones in Area 1 New Program Only Enter the zone numbers of zones to be used as Exit Entry zones Valid entries are from 01 to 32 Directly en...

Страница 8: ...NEXT YES button to enable Press the PRIOR NO button to continue The SIA CP 01 Features are designed to reduce the incidence of false alarms See WI808 Installer Program ming Quick Reference Chart SIA...

Страница 9: ...s with Area 1 and Area 2 Options Press R once to set the cursor to the User Code Use the number buttons 1 through 9 to enter a code from 3 to 6 digits Enter up to 6 digits 4 digits is recommended in t...

Страница 10: ...sarm this area Arm Only Prevents User Code from disarming this area Service A Service Code has restricted arm disarm rights if an area is armed with a Service Code a MONITOR ON appears on the GEM RP2A...

Страница 11: ...panic buttons on a system each reporting to a Central Station or a pager and or annunciating on a keypad the key fob zone number with description location To assign a key fob to a zone program the key...

Страница 12: ...U button Data entry is not allowed NOTE Enter Easy Menu Driven Program Mode to program system again Cold Start Erases Entire Program This erases the entire program including Dealer Program by erasing...

Страница 13: ...tions Fire Zones Appears for New Panel Only Enter the zone number of any Fire Zones both 2 wire 4 wire or wireless Valid entries are from 01 to 32 Directly enter each zone number including leading zer...

Страница 14: ...rogram Only Enter the zone numbers of zones to be used as Exit Entry zones Valid entries are from 01 to 32 Directly enter each zone number including leading zeros Press U to save and repeat for any ad...

Страница 15: ...YES button to program all zones except 24 Hr fire zones for No End Of Line Resistor Press the PRIOR NO button to continue Do not program this feature for UL Installations Enable Telco Line Fault Test...

Страница 16: ...s for each code Refer to the tables below for available data entries for User Options Press R once to set cursor to the User Number and enter the desired User Number Press R once again to set the curs...

Страница 17: ...h 27 displayed in keypad window press R 0 2 User 2 R 1234 G 0 G 0 User Code 09 User Area 1 options 00 User Area 2 Options and U save Notes 1 For User Code press G 0 for Blank Space 2 For User Options...

Страница 18: ...ng leading zeros Use the 1 through 9 buttons NOTE Press 0 for a zero Press U to save Re enter the Dealer Code to verify the previous code Press U to save Press the NEXT YES but ton to proceed NOTE The...

Страница 19: ...L NAPCO Security Systems X GEM P1632 Programming Instructions Page 19 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 20: ...nge all the options It consists of multiple address locations with two data entry locations each left and right as shown in the adjacent diagram ACCESSING DIRECT ADDRESS PROGRAM MODE LEFT DIGIT RIGHT...

Страница 21: ...M K3DGTL Keypads To access press C in Dealer Program Mode 1 Toggle Cursor to 4 digit ad dress field using the R button 2 Enter address Number directly using number buttons 0 9 3 Enter Data directly us...

Страница 22: ...KEYPAD DISPLAYS 8 4 2 1 blank 0 8 4 2 1 1 1 8 4 1 2 2 2 8 4 3 3 3 8 2 1 4 4 4 8 2 5 5 5 8 1 6 6 6 8 7 7 7 4 2 1 8 8 8 4 2 9 9 9 4 1 10 G 0 0 4 11 G 1 B 2 1 12 G 2 C 2 13 G 3 D 1 14 G 4 E 15 G 5 F DATA...

Страница 23: ...ch address CONVENTIONS USED IN THIS MANUAL The Keypad Programming Worksheets in the back are provided as an address programming reference to help the installer modify his custom default program or to...

Страница 24: ...try in the boxes shown 4 For more information on a programming option refer to the Glossary at the end of this manual EXIT ADDRESS 0000 DELAY LEFT RIGHT sec Default 3 C ENTRY ADDRESS 0001 DELAY 1 LEFT...

Страница 25: ...save PAGER FORMAT OPTIONS ADDRESS 0256 0257 LEADING DIGITS FOR PAGER FORMAT In Pager Format reporting the message typically begins with 00 However for some pager services this will cause the Pager s...

Страница 26: ...Output 8 4 2 1 0463 8 4 2 1 Report Event Telco 1 8 4 2 1 0464 8 4 2 1 Report Restore Telco 1 8 4 2 1 0465 8 4 2 1 Report Event Telco 3 8 4 2 1 0468 8 4 2 1 Report Restore Telco 3 8 4 2 1 0469 8 4 2 1...

Страница 27: ...PTIONS 1 Auto Bell Test on Arming 2 Auto Reset after Burglary Output Timeout 4 Suppress Bypass Reminder when Armed 8 Enable Local Alarm on First Zone AND Trip RIGHT DATA VALUES CIRCLE SYSTEM OPTIONS 1...

Страница 28: ...S CIRCLE SYSTEM OPTIONS 1 Enable Keypad Set Time Date Message 2 Enable Cancel Report to Telco 3 4 Disable ON OFF as Easy Exit 8 Enable GEM PRINT Module Lug E15 Output Mode ADDRESS 1061 LEFT RIGHT blan...

Страница 29: ...E Leave trailing boxes blank For a zero press G0 3 Valid entries are 1 9 B button C button D 3 sec pause E Wait for dial tone F ignore location Press U or D to save Default for CS R e c e i v e r 1 Te...

Страница 30: ...TS 1 4 CS Telco 3 Subscriber 0303 0304 0305 0306 Opening Closing ID R R R R Number Area 2 ADDRESS 0303 0306 RIGHT DIGITS 1 4 CS Telco 1 Subscriber 0267 0268 0269 0270 Event ID R R R R Number Area 1 AD...

Страница 31: ...t digit is 3 then the reporting code is 39 For example for zone 15 address 0372 if the right digit is 4 then the reporting code is 45 MODEM CODES determine the zone types reported for the following fo...

Страница 32: ...r 11 User 10 User 9 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUES ADDRESS 0448 User Closing Telco 1 User 32 User 31 User 30 User 29 LEFT RIGHT User 28 User 27 User 26 User 25 8 4 2 1 8 4 2 1 RIGH...

Страница 33: ...aded data value box shows option not available 3 Press U or D to save AREA ARMING OPTIONS ADDRESS 0743 0744 PRIORITY AREA ARMING 1 Select option from the table shown 2 Enter in corresponding right dig...

Страница 34: ...NOTE Dark shaded data value box shows option not available 4 Press U or D to save Area Bell Control Options RIGHT DATA VALUES CIRCLE Disarming Area 1 1 Area 1 Burg Output Silenced 2 Area 2 Burg Outpu...

Страница 35: ...in corresponding right and left digit address locations above 3 Press U or D to save KEYPAD OPTIONS ADDRESS 0723 0736 RIGHT OPTION blank Disabled 1 Active Keypad KEYPAD ASSIGNMENT KEYPAD NO KEYPAD OPT...

Страница 36: ...ower 8 4 2 1 0561 8 4 2 1 8 4 2 1 0506 8 4 2 1 Auto Reset 8 4 2 1 0562 8 4 2 1 8 4 2 1 0507 8 4 2 1 Swinger Shutdown 8 4 2 1 0563 8 4 2 1 8 4 2 1 0508 8 4 2 1 Chime 8 4 2 1 0564 8 4 2 1 8 4 2 1 0509 8...

Страница 37: ...2 1 8 4 2 1 0612 8 4 2 1 PGM2 Output 8 4 2 1 0668 8 4 2 1 8 4 2 1 0613 8 4 2 1 Entry Exit 1 8 4 2 1 0669 8 4 2 1 8 4 2 1 0614 8 4 2 1 Entry Exit 2 8 4 2 1 0670 8 4 2 1 8 4 2 1 0615 8 4 2 1 Exit Entry...

Страница 38: ...811 0812 0813 L R L R L R L R L R 0814 RELAY AREA Timeout Event ID COND ADDRESS 0815 0819 RELAY EVENT 14 0815 0816 0817 0818 L R L R L R L R L R 0819 RELAY AREA Timeout Event ID COND ADDRESS 0820 0824...

Страница 39: ...D 8 Area 1 General System Alarm D 9 Area 2 General System Alarm F blank Relay Control Group 1 F 1 Relay Control Group 2 F 8 Entry Relay Area 1 F 9 Entry Relay Area 2 LEFT DATA ENTRIES ALARM TYPE TIMEO...

Страница 40: ...locations above right digit only left digit is not used 3 Press U or D to save NOTE These timers apply only to Supervised RF Transmitters see RF Transmitters in Easy Menu Driven Mode Programming Defa...

Страница 41: ...sed for programming however this keypad may be located in any area The Program Mode cannot be accessed while the communicator is transmitting except during the first three minutes after power up After...

Страница 42: ...s directly using number buttons 0 9 4 Press the U button to save each code NOTE Press G 0 button to clear character at cursor To continue press P or Q button G E M I N I ARMED COMPUTERIZED SECURITY SY...

Страница 43: ...panel Keypads 1 7 Each must be configured for a keypad address In addition the keypad may be configured to disable a touchpad backlight b LCD backlight and c entry sounder Keypads are configured by t...

Страница 44: ...dress 0720 27 Clear Dealer Program Direct Address 1197 41 Closing Report Only on Conditional Close Direct Address 0718 27 Cold Start Direct Address 1198 41 CS AREA SYSTEM REPORTING OPTIONS Direct Addr...

Страница 45: ...or Stay Bypass Enable Zone Direct Address 0528 0583 0638 0693 36 37 Interior Normally Bypassed Direct Address 0720 27 Key fob Transmitters Easy Menu Driven N A 11 18 KEYPAD OPTIONS Direct Addresses 07...

Страница 46: ...sses 0478 0485 26 SYSTEM RESPONSE ACTIVATED BY GLOBAL EVENT TROUBLE Direct Addresses 0460 0469 26 Test Timer Direct Address 0332 30 Touch tone Dialing w Rotary Backup Direct Address 0394 31 Trouble on...

Страница 47: ...0 0319 0350 CENTRAL STATION SYSTEM REPORTING CODES Direct Addresses 30 0330 Cancel Report Code Direct Address 30 0332 Test Timer Direct Address 30 0358 0389 CS ZONE REPORTING OPTIONS Direct Addresses...

Страница 48: ...t Address 36 37 0538 Sensor Watch Enable Zone Direct Address 36 37 0540 Chime 2 Enable Zone Direct Address 36 37 0546 Priority Enable Zone Direct Address 36 37 0547 Priority with Bypass Enable Zone Di...

Страница 49: ...ct Address 36 37 0617 Auto Reset Enable Zone Direct Address 36 37 0618 Swinger Shutdown Enable Zone Direct Address 36 37 0619 Chime Enable Zone Direct Address 36 37 0620 Abort Delay Enable Zone Direct...

Страница 50: ...Address 36 37 0690 Trouble on Short Enable Zone Direct Address 36 37 0691 Zone Area 1 Enable Zone Direct Address 36 37 0692 Zone Area 2 Enable Zone Direct Address 36 37 0693 Interior Stay Bypass Enab...

Страница 51: ...e Low Battery Direct Address 27 0722 Veri phone Priority Zones over Alarms Direct Address 27 0722 Veri phone Audio Priority Over Alarms Direct Address 27 0722 Veriphone Zones trip PGM2 Output Direct A...

Страница 52: ...REFER TO WI808 FOR COMPATIBLE TWO WIRE SMOKE DETECTORS DO NOT MIX DIFFERENT MODELS 7 RECOMMENDED BATTERIES YUASA NP4 12 OR NP7 12 BATTERY SHOULD BE REPLACED EVERY 5 YEARS 8 THIS PANEL SHALL BE CHECKED...