240
8-5. System Registers
Address
418
Name of system register
Buffer capacity setting
for data received
from RS232C serial port
Default
value
K1660
Description
This register specifies the number of words to be used as
a buffer. (Refer to system register 417 on page 239 for
details about the starting address settings.)
• Setting range
C24C/C40C types: K0 to K1660
C56C/C72C types: K0 to K6144
EXAMPLE:
If K0 is input to system register 417 and K100 to system
register 418, the number of data received is stored to DT0
and the data received are stored starting from DT1 to DT99.