233
8-5. System Registers
Address
7
8
14
20
26
31
Name of system register
Hold area starting
address settings for
internal relays
Hold area starting
address settings for
data registers
Hold/non-hold setting for
step ladder
Operation settings for
duplicated use of output
Operation settings when
an operation error occurs
Waiting time settings for
multi-frame communication
Default
value
K10
K0
K1
K0
K0
K2600
(6500 ms)
Description
Hold area starting address for internal relays is specified in
word-units.
• Setting range
C14/C16 series:
C24/C40/C56/C72 series:
• If the maximum value of the setting range is input, all of
the areas are used as non-hold areas.
EXAMPLE:
If system register 7 of C14 series is set to K5:
- Non-hold area:
- Hold area:
Hold area starting address for data registers is specified.
• Setting range
C14/C16 series: K0 to K256
C24/C40 series: K0 to K1660
C56/C72 series: K0 to K6144
• If the maximum value of the setting range is input, all of
the areas are used as non-hold areas.
EXAMPLE:
If the system register 8 of C14 series is set to K10:
- Non-hold area:
- Hold area:
Hold/non-hold setting for step ladder operation is specified.
K0: Hold
K1: Non-hold
This register specifies the operation of the FP1 when a
duplicated use of output is programmed.
K0: a duplicated use of output is regarded as a
total-check error.
K1: a duplicated use of output is not regarded as an
error.
This register specifies the operation of the FP1 when an
operation error is detected.
K0: FP1 stops operation if an operation error occurs.
K1: FP1 continues operation even if an operation error
occurs.
This register specifies the maximum waiting time between
delimiters when multi-frame communication is performed
with the computer link.
• Setting range
K4 to K32760: 10 ms to 81.9 s
• The formula to calculate the waiting time is:
set value
×
2.5 ms
Note:
- When you set this register using NPST-GR Software, set
a time that can be divided by 2.5.
K0 to K16
K0 to K63
R0 to R4F
R50 to R15F
DT0 to DT9
DT10 to DT255