All rights reserved ©N1 Critical Technologies, Inc.
NE Series (20-30kVA)
User Manual
Chapter 4 Operation Guide
The setting range of bypass voltage lower threshold is -15%, -20%, -25%;
The range of bypass frequency is:±5%, ±10%.
Figure4-31 System management page 2
ECO mode: on, off;
ECO voltage upper threshold: +10%, +15%;
ECO voltage lower threshold: -10%, -15%.
After changing the parameter, it is necessary to click
button to save the setting. If the setting
is successful, there will be a icon at the right side of the parameter, as shown in Figure4-32, if
setting is unsuccessful, there will be a icon at the right side of the parameter, as shown in
Figure4-33.