11
All rights reserved ©N1 Critical Technologies, Inc.
NE Series (20-30kVA)
User Manual
Chapter 2 Overview
Figure2-5 Operation interface of NE Series (20-30kVA) UPS
The description for the operation interface of NE Series (20-30kVA) UPS is as shown in Table2-1.
Table2-1 Definition of operation interface
No.
Silk-screen Name
Description
1
-
Touch screen
Display the UPS parameters and status (such as
voltage, current, load, etc.)
2
BYPASS
Bypass indicator
Green: Bypass output
Red: Bypass abnormal
Light off: Bypass normal but with no output
3
BATT.
Battery low-voltage
alarm indicator
Red: Battery abnormal alarm (it will flicker if
battery low-voltage alarm)
Green: Battery voltage normal
4
AC/DC
Rectifier indicator
Green: Rectifier works normally
Red: Rectifier fault and protected
Light off: Rectifier is not working.
5
DC/AC
Inverter indicator
Green: Inverter works normally.
Red: Inverter fault and protected.
Light off: Inverter is with no output
.
6
LOAD
Load alarm
indicator
Red: output abnormal
Green: Output normal