Installation
MSA
ULTIMA X ® Series
GB
33
Fig. 7
Connections on the instrument board
This shows all possible ULTIMA XE connections, three wire with 4-20 mA output
and HART Protocol.
ULTIMA X
®
Series Gas Monitors can be connected to all control units that process
4-20 mA analogue signals [such as SUPREMA, 9010/9020, DCS etc.]
The power supply requirements are given in chapter 7. In addition, refer to:
-
installation drawings [
Chapter 9.1 to 9.5]
-
cable lengths and cross-sections [
-
connection drawings for controllers [
TROUBLE RELAY CONNECTOR
HART PORT CONNECTOR
'J8' POWER CONNECTOR
SENSOR CONNECTOR
ALARM RELAY CONNECTIONS
PUSH BUTTON
CONNECTOR
If using the HART signal terminate the 4-20 mA line with 230 to
500 Ohms
Attention!
When using any of the ULTIMA X
®
Series options [such as relays] with
4-20 mA output signal, a 3-wire connection must be used. Failure to use
a 3-wire connection could damage the electronics in the
ULTIMA X
®
Series Gas Monitor.
Содержание ULTIMA X-Series
Страница 1: ...Operating Manual ULTIMA X Series Gas Monitors Order No 10046690 09 ...
Страница 2: ...MSA AUER GmbH Thiemannstrasse 1 D 12059 Berlin Germany MSA AUER GmbH All rights reserved ...
Страница 28: ...MSA Description ULTIMA X Series 28 GB Fig 5 ULTIMA XA Fig 4 ULTIMA Remote sensor module non reactive gas ...
Страница 69: ...Appendix Electrical Installation MSA ULTIMA X Series GB 69 9 3 Installation Outline Drawing CE ULTIMA XA ...
Страница 72: ...MSA Appendix Electrical Installation ULTIMA X Series 72 GB 9 6 HART module M6 109 45 4 309 ...
Страница 158: ...MSA Appendix HART Specific Information ULTIMA X Series 158 GB Sensor Trim Point Screen Fig 52 Sensor trim point screen ...