Technical Data
ULTIMA X ® Series
56
GB
7.2
Performance Specifications
*)
In the extended temperature range, the sensor may not meet all the specified pa-
rameters
**)
Response time t90 may increase up to 50 seconds when used with SensorGard.
Gas types
Combustible gases, oxygen and toxic gases
Tempera-
ture range
Toxic gases and
oxygen
Operating range
0 °C to 40 °C
Extended range
*)
-20 °C to +50 °C
Operating range NH
3
0 °C to 30 °C
Extended range NH
3
;
CL
2
; ClO
2
*)
-10 °C to 40 °C
Calibrate within operating temperature range.
Combustible
gas, catalytic
Single module
-40 °C to +60 °C
Dual module
Combustible
gas, IR
Single module
-40 °C to +60 °C
Dual module
Drift
Zero drift
Less than 5 % per year,
typically XIR Ethylene:
4 % per 3 months
Span drift
Less than 10 % per year, typically
Noise
Less than 1 % FS
Warm up time
Less than 45 sec
Storage temperature
-40 °C to +60 °C or limits of the sensor
Step change
response
Time to reach
20 % of scale -
Toxics
Less than 12 sec
[typically 6 sec]
Less than 20 sec
Time to reach
50 % of scale -
Toxic
Less than 30 sec
[typically 12 sec]
Less than 45 sec
Response
time with
sensor
Gas
ULTIMA XE Oxygen
t20
t90
Oxygen
10 sec
40 sec
**)
Содержание ULTIMA X-Series
Страница 1: ...Operating Manual ULTIMA X Series Gas Monitors Order No 10046690 09 ...
Страница 2: ...MSA AUER GmbH Thiemannstrasse 1 D 12059 Berlin Germany MSA AUER GmbH All rights reserved ...
Страница 28: ...MSA Description ULTIMA X Series 28 GB Fig 5 ULTIMA XA Fig 4 ULTIMA Remote sensor module non reactive gas ...
Страница 69: ...Appendix Electrical Installation MSA ULTIMA X Series GB 69 9 3 Installation Outline Drawing CE ULTIMA XA ...
Страница 72: ...MSA Appendix Electrical Installation ULTIMA X Series 72 GB 9 6 HART module M6 109 45 4 309 ...
Страница 158: ...MSA Appendix HART Specific Information ULTIMA X Series 158 GB Sensor Trim Point Screen Fig 52 Sensor trim point screen ...