78
Technical Data
ALTAIR io360
US
11.3 Factory Set Alarm Thresholds and Set Points
11.3.1 Calibration Gas Defaults
Calibration gas, Part Number 10048890
Check the monitor or calibration certificate for exact alarm levels as they vary depending on
national or corporate regulations.
Sensor
Low Alarm
High Alarm
Min. Alarm Set Point
Max. Alarm Set Point
Combustible (%LEL) 10
20
5
60
O
2
(% vol)
19.5
23.0
5.0
24.0
H
2
S (ppm)
5
10
5
175
CO (ppm)
25
100
10
1700
Sensor
Default Calibration
Set point
Minimum Calibration
Set point
Maximum Calibration
Set point
Combustible (% LEL) 50
5
100
O
2
(% vol)
15.0
5.0
30.0
H
2
S (ppm)
20
5
200
CO (ppm)
60
10
1700
Feature
Options
Detector password
App supports up to 6 digit numeric values
Calibration Due days
1 - 180, default is off
Periodic log collection rate
30 minutes
Frontlight timeout
30 seconds
Gas measurement Units
Combustible
% LEL or % vol
Toxic
ppm
O
2
% vol
Gas
Default Cal Units
CO
60
PPM
O
2
15.0 %
VOL
H
2
S
20
PPM
Combustible
50.0 %
LEL