36
Deployment
ALTAIR io360
US
5.2.2 HUB
The HUB placement:
• Ambient temperature range: -20°C to +60°C
• Humidity Range: 10 to 95 % r.H. (non-condensing)
• Environments classified as pollution degree 1 or 2
Avoid exposure to weather to reduce excessive wear.
WARNING!
The HUB is designed and intended for use where the altitude is less than 2,000m (6,500 ft). Use of the HUB
above this altitude can results in current surges, temporary over-voltage, and arcing which can result in a
loss of HUB functionality and fire.
Failure to follow this warning can result in serious personal injury or death.
Powering the HUB
Option 1:
Option 2:
(1) Power the HUB in a non-hazardous location.
(2) Move the HUB to its mounting location.
Mounting the HUB
(1) Connect Ethernet (optional).
(2) Connect Power to HUB assembly.
(3) Connect power to mains supply in non-hazardous location.
After the HUB is powered, mount HUB to its final location. Mount HUB to
its final location is valid for both option 1 and 2. It needs to follow option 1
and 2.
Use four screws to fasten the wall brackets to the surface and apply a
torque of 45 in-lb +/- 5 in-lb (5 Nm +/- 1 Nm).
NOTE:
It is the customer's responsibility to ensure the mounting system is
properly chosen and installed such that it is capable of supporting 20
pounds of weight. Ensure the connectors and wires are supported to
remove the stress and strain on the HUB.