5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
45
7545652/00 EN
VACUTAP
®
VR-Ex
5.3.1.2 Fastening oil compartment to transformer cover – separable on-load
tap-changer head
In on-load tap-changers with U
m
≥ 362 kV, you cannot lower the oil compart-
ment through the opening in the mounting flange from above, because the
diameter of the shielding rings is greater than the inner diameter of the
mounting flange. In this case, you must first lift the top part of the on-load
tap-changer head off of the bottom part and fasten the top part to the trans-
former cover. You can then fasten the oil compartment to the top part of the
on-load tap-changer head.
5.3.1.2.1 Lifting top part of on-load tap-changer head off supporting flange
(bottom part)
5.3.1.2.1.1 Removing on-load tap-changer head cover
NOTICE
Damage to the on-load tap-changer!
Small parts in the oil compartment may block the diverter switch insert,
thereby damaging the on-load tap-changer.
► Ensure that parts do not fall into the oil compartment.
► Check that all small parts are accounted for.
1.
CAUTION!
An unstably positioned oil compartment may tip over, re-
sulting in injuries or property damage. Place the oil compartment on a
level surface and secure it against tipping.
2. Remove red-colored packaging material and transport material from the
oil compartment.
3. Ensure that the inspection window is sealed off with the cover.
4. Remove the screws and washers from the on-load tap-changer head
cover.
Figure 21: On-load tap-changer head cover
Содержание VACUTAP VR-Ex
Страница 73: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 73 7545652 00 EN VACUTAP VR Ex Figure 70 VACUTAP VRS ...
Страница 74: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 74 7545652 00 EN VACUTAP VR Ex Figure 71 VACUTAP VRM VRH VRX ...
Страница 75: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 75 7545652 00 EN VACUTAP VR Ex Figure 72 VACUTAP VRM VRH VRX ...
Страница 76: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 76 7545652 00 EN VACUTAP VR Ex Figure 73 VACUTAP VRL VRH ...
Страница 77: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 77 7545652 00 EN VACUTAP VR Ex Figure 74 VACUTAP VRL VRH ...
Страница 234: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 234 7545652 00 EN VACUTAP VR Ex 9 Drawings 9 1 Dimensional drawings ...
Страница 237: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 237 7545652 00 EN VACUTAP VR Ex 9 2 On load tap changer head ...
Страница 238: ......
Страница 241: ......
Страница 242: ......
Страница 243: ......
Страница 244: ......
Страница 245: ......
Страница 246: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 246 7545652 00 EN VACUTAP VR Ex 9 3 Adjustment plans ...
Страница 254: ......
Страница 255: ......