7 Fault elimination
Maschinenfabrik Reinhausen GmbH 2020
224
7545652/00 EN
VACUTAP
®
VR-Ex
93025 Regensburg
Germany
Phone: +49 94140 90-0
Fax: +49 9 41 40 90-7001
E-mail: [email protected]
Internet: www.reinhausen.com
Fault description
Action
Tripping of protective relay (for example RS-Ex)
See "Tripping of the protective relay and re-commissioning
the transformer".
Also contact MR.
Activation of rupture disk in on-load tap-changer head
cover
On-load tap-changer and transformer must be checked.
Depending on the cause of tripping, take measurements /
carry out checks on the transformer.
Contact MR to check the on-load tap-changer.
Tripping of motor protective switch in motor-drive unit
See the "Fault elimination" chapter in the operating instruc-
tions of the TAPMOTION® ED-Ex motor-drive unit.
Tripping of signaling contact that indicates that the oil level
has fallen below the minimum oil level in the on-load tap-
changer oil conservator
Check pipe system (pipes etc.) and on-load tap-changer
head for leaks. Check oil level and oil quality of diverter
switch oil in accordance with operating instructions for on-
load tap-changer. If the fill level has fallen below the limit
values, also contact MR.
On-load tap-changer not changing tap position (sluggish-
ness, Raise keys / Lower keys not working, no audible di-
verter switch action)
Contact MR.
No change in voltage on transformer despite change in po-
sition on motor-drive unit
Contact MR.
Tap position indicator on motor-drive unit and on-load tap-
changer different
Contact MR.
Noises on drive shaft or motor-drive unit when changing
tap position
Ensure proper mounting of the drive shaft in accordance
with its operating instructions. Check that hose clips and
protective covers are seated correctly. Contact MR in the
event of noise from the motor-drive unit.
Red message on monitoring unit
If possible read out database and send to MR along with
error code.
Warning or tripping of Buchholz relay on transformer
Notify manufacturer of transformer.
Deviation from desired value when measuring winding re-
sistance of transformer
Contact manufacturer of transformer and, if necessary,
MR, and provide measured values.
Deviation from desired value during dissolved gas analysis
(transformer oil)
Contact manufacturer of transformer and, if necessary,
MR, and provide measured values.
Deviation from desired value during transformer ratio test
Contact manufacturer of transformer and, if necessary,
MR, and provide measured values.
Deviation from limit value for insulating fluids
Carry out insulating fluid change, check oil conservator
breather of on-load tap-changer.
Table 14: Fault elimination
Содержание VACUTAP VR-Ex
Страница 73: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 73 7545652 00 EN VACUTAP VR Ex Figure 70 VACUTAP VRS ...
Страница 74: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 74 7545652 00 EN VACUTAP VR Ex Figure 71 VACUTAP VRM VRH VRX ...
Страница 75: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 75 7545652 00 EN VACUTAP VR Ex Figure 72 VACUTAP VRM VRH VRX ...
Страница 76: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 76 7545652 00 EN VACUTAP VR Ex Figure 73 VACUTAP VRL VRH ...
Страница 77: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 77 7545652 00 EN VACUTAP VR Ex Figure 74 VACUTAP VRL VRH ...
Страница 234: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 234 7545652 00 EN VACUTAP VR Ex 9 Drawings 9 1 Dimensional drawings ...
Страница 237: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 237 7545652 00 EN VACUTAP VR Ex 9 2 On load tap changer head ...
Страница 238: ......
Страница 241: ......
Страница 242: ......
Страница 243: ......
Страница 244: ......
Страница 245: ......
Страница 246: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 246 7545652 00 EN VACUTAP VR Ex 9 3 Adjustment plans ...
Страница 254: ......
Страница 255: ......