5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
140
7545652/00 EN
VACUTAP
®
VR-Ex
3. Remove on-load tap-changer head cover.
Figure 144: On-load tap-changer head cover
5.4.5.1.3 Drying the on-load tap-changer
NOTICE
Damage to the on-load tap-changer head cover and on-load tap-
changer accessories.
Both the on-load tap-changer head cover and the on-load tap-changer ac-
cessories will become damaged if they are dried.
► Never dry the on-load tap-changer head cover or the following acces-
sories: motor-drive unit, drive shaft, protective relay, pressure monitoring
device, pressure relief device, bevel gear, temperature sensor, oil filter
unit.
1. Heat up the on-load tap-changer in air at atmospheric pressure with a
temperature increase of approximately 10 °C/h to a final temperature of
maximum 110 °C.
2. Pre-dry the on-load tap-changer in circulating air at a maximum tempera-
ture of 110 °C for a period of at least 20 hours.
3. Vacuum-dry on-load tap-changer at between 105 °C and maximum
125 °C for at least 50 hours.
4. Residual pressure of no more than 10
-3
bar.
5.4.5.1.4 Securing on-load tap-changer head cover
NOTICE
Damage to the on-load tap-changer!
A missing or damaged o-ring as well as unclean sealing surfaces lead to in-
sulating fluid escaping and therefore to damage to the on-load tap-changer.
► Ensure that the o-ring is positioned untwisted in the on-load tap-changer
head cover.
► Ensure that the o-ring does not become damaged when mounting the
cover.
► Ensure that the sealing surfaces on the on-load tap-changer head cover
and on-load tap-changer head are clean.
Содержание VACUTAP VR-Ex
Страница 73: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 73 7545652 00 EN VACUTAP VR Ex Figure 70 VACUTAP VRS ...
Страница 74: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 74 7545652 00 EN VACUTAP VR Ex Figure 71 VACUTAP VRM VRH VRX ...
Страница 75: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 75 7545652 00 EN VACUTAP VR Ex Figure 72 VACUTAP VRM VRH VRX ...
Страница 76: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 76 7545652 00 EN VACUTAP VR Ex Figure 73 VACUTAP VRL VRH ...
Страница 77: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 77 7545652 00 EN VACUTAP VR Ex Figure 74 VACUTAP VRL VRH ...
Страница 234: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 234 7545652 00 EN VACUTAP VR Ex 9 Drawings 9 1 Dimensional drawings ...
Страница 237: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 237 7545652 00 EN VACUTAP VR Ex 9 2 On load tap changer head ...
Страница 238: ......
Страница 241: ......
Страница 242: ......
Страница 243: ......
Страница 244: ......
Страница 245: ......
Страница 246: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 246 7545652 00 EN VACUTAP VR Ex 9 3 Adjustment plans ...
Страница 254: ......
Страница 255: ......