5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
128
5293079/01 EN
VACUTAP
®
VM-Ex
2. Insert lifting gear in the brackets provided on the diverter switch insert car-
rier plate and position vertically above the diverter switch insert.
Figure 142: Brackets on carrier plate
3. Lift out diverter switch insert slowly and vertically.
Figure 143: Lifting out diverter switch insert
4.
CAUTION!
Place the diverter switch insert on a level surface and se-
cure it against tipping. An unstably positioned diverter switch insert may
tip, resulting in injuries and property damage.
5. Note down whether the diverter switch insert is in the final end position on
side A or side B. If the diverter switch insert is in the final end position on
side A, the vacuum interrupter on side A is closed, and vice versa. In the
example in the appendix, the diverter switch insert is in the final end posi-
tion on side B, see appendix.
5.4.8.2.2 Opening kerosene drain plug
►
NOTICE!
Never remove the kerosene drain plug completely. Unscrew
kerosene drain plug with extended socket wrench counter-clockwise until
it starts to become hard to open.