6 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
173
5293079/01 EN
VACUTAP
®
VM-Ex
6 Commissioning
WARNING
Danger of explosion!
Explosive gases in the oil compartment of the on-load tap-changer, trans-
former, pipework system, oil conservator and at the dehydrating breather
opening can deflagrate or explode and result in severe injury or death!
► Ensure that there are no ignition sources such as naked flame, hot sur-
faces or sparks (e.g. caused by the build-up of static charge) in the trans-
former's immediate surroundings during commissioning and that none oc-
cur.
► Do not operate any electrical devices (e.g. risk of sparks from impact
wrench).
► Only use conductive and grounded hoses, pipes, and pump equipment
that are approved for flammable liquids.
WARNING
Danger of explosion!
Overloading the on-load tap-changer can lead to explosion. Spraying hot in-
sulating fluid and flying parts can lead to death and serious injuries. Prop-
erty damage is highly probable.
► Ensure that the on-load tap-changer is not overloaded.
► Ensure use of the on-load tap-changer in accordance with section "Ap-
propriate use".
► Prevent operations outside of the permitted operating conditions by tak-
ing suitable measures.
6.1 Commissioning the on-load tap-changer at the transformer
manufacturer's site
Perform the following work and functional checks before commissioning the
transformer.
6.1.1 Bleeding on-load tap-changer head and suction pipe
6.1.1.1 Bleeding on-load tap-changer head
1. Open all forward valves and return valves in the pipe system.