5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
125
5293079/01 EN
VACUTAP
®
VM-Ex
3.
NOTICE!
Remove the on-load tap-changer head cover. Make sure that
sealing surfaces on the on-load tap-changer head cover and on-load tap-
changer head are in sound condition when removing and during all other
work and that the o-ring is also undamaged. Damaged sealing surfaces
lead to oil escaping and therefore to on-load tap-changer and transformer
damage.
Figure 135: On-load tap-changer head cover
5.4.8.2.1.3 Removing tap position indicator disk without multiple coarse change-
over selector
► Pull spring clip off shaft end and remove tap position indicator disk.
Figure 136: Tap position indicator disk
5.4.8.2.1.4 Removing tap position indicator disk with multiple coarse change-over
selector with more than 35 operating positions
1. Ensure that the red marks on the panel, tap position indicator disk and
cover disk produce a continuous red line.