5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
59
5293079/01 EN
VACUTAP
®
VM-Ex
With coarse tap selector connection, the external appearance of the (+) and
(-) change-over selector connection contacts is identical to the tap selector
contacts (through-hole for M10 screws, always in vertical position).
1. Fasten the tap-winding connecting leads to the change-over selector in
accordance with the connection diagram provided. The cable shoes and
fastening materials are not included in the scope of delivery.
2. Take suitable measures to ensure that each fitting cannot come loose or
settle (e.g. by using clamping washers). Be sure to attach the screening
caps if these are included in the delivery scope.
3. Close the screening caps and make sure they are seated correctly. The
screw head and nut must be fully covered.
Figure 41: Change-over selector connection contacts for coarse tap selector connection