6 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
182
5293079/01 EN
VACUTAP
®
VM-Ex
2. Remove screw cap on air-vent valve E1 on the on-load tap-changer head
cover.
Figure 214: Screw cap
3. Use screwdriver to lift valve tappet on air-vent valve E1 and bleed on-load
tap-changer head.
Figure 215: Valve tappet
4. Seal air-vent valve E1 with screw cap (tightening torque 10 Nm).