7 Operation
Maschinenfabrik Reinhausen GmbH 2021
92
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
7.4.14 Read out software version (F6)
To read out the software version, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1.
> Press
until the desired function is displayed.
ð
2. Press
to confirm the selection.
ð
The control unit's software version is displayed.
3. Press
to exit the display.
4. Press
to leave the parameterization menu.
7.4.15 Customer message for event messages E1 and E2 (F7)
You can set whether the event messages E1
EXTERNAL CONTROL
and
E2
Remote control
are to be reported via the customer messages interface
Ready/Error
(terminal X5). All further event messages will always be re-
ported via the customer messages interface
ready/error
(terminal X5).
7.4.15.1 Customer message for event message E1 (F7.1)
With this function, you can set whether the event message E1
EXTERNAL
CONTROL
is to be reported via the customer messages interface
Ready/Er-
ror
(terminal X5). You can select the following options:
▪ 0: inactive
▪ 1: active
To set the customer message for event message E1, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired function is displayed.
ð
2. Press
to confirm the selection.
ð
3. Press
to confirm the selection.
4. Press
or
to select the desired option.
5. Press
to confirm the selection.
6. Press
to save the setting.