5 Mounting
Maschinenfabrik Reinhausen GmbH 2021
36
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
9.
NOTICE!
Using the emergency drive shaft, turn for every tap-change op-
eration in one direction until one revolution has been completed and the
arrow on the cam disk (1) is again pointing to the arrow in the cover (2).
Otherwise, the tap-change operation has not been completed correctly,
which may result in damage to the on-load tap-changer and transformer.
Figure 15: Position of the shaft of the on-load tap-changer
ð
The current operating position is displayed by the control wheel.
Figure 16: Checking operating position (example illustration)
10. Pull the emergency drive shaft out of the shaft of the on-load tap-
changer and plug it back into the bracket.
Figure 17: Plugging the emergency drive shaft back in