6 Commissioning
Maschinenfabrik Reinhausen GmbH 2021
50
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
1. Ensure that the motor-drive unit is positioned correctly: The feather key
on the motor-drive unit must be facing the marking
:
Figure 30: Checking the position of the motor-drive unit
2. Ensure that the on-load tap-changer is positioned correctly: The marking
on the cam disk
must be within the marked range of the cover
:
Figure 31: Checking the position of the on-load tap-changer
3. Mount and connect motor-drive unit and control unit.
Commissioning
NOTICE
Damage to device and system periphery
An incorrectly connected device can cause damage to the device and sys-
tem periphery.
► Check the entire configuration before commissioning.
► Make sure that the supply voltage (= measured voltage) corresponds to
the specifications in the technical data.