5 Mounting
Maschinenfabrik Reinhausen GmbH 2021
43
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
Connecting the control unit
1. Connect the 5-wire connection cable of the motor-drive unit to terminal X4
(0.4 Nm).
2. Connect the 2-wire connection cable of the motor-drive unit to terminal X2
(0.5 Nm).
Figure 25: Connection cable connection
3.
DANGER!
Ensure that the connections PE, N, and L are not inter-
changed. Otherwise, dangerously high voltages could occur at the hous-
ing. Tighten (0.5 Nm) the control unit power supply to the plug connector
for X1 in accordance with the supplied connection diagram. In addition,
use the green cable housing supplied for touch protection.
4. The plug connector is coded. Carry out the installation without using force.
Connect the plug connector to terminal X1 correctly according to the de-
vice labeling and screw it tight with 0.5 Nm.