9 Fault elimination
The transformer can be operated in the current operating position safely de-
spite the red signal light. Further switching operations are blocked.
9.1 General faults
Characteristics/details
Cause
Remedy
No function
▪
LED not lit up
No voltage supply
Check the voltage supply.
Device-internal fuse (F1) tripped
Check fuse (F1) and replace if necessary.
Table 20: General faults
9.2 Problem with automatic voltage regulation (AVR AUTO)
Characteristics/details
Cause
Remedy
Automatic voltage regulation not
functioning.
Bandwidth set too high.
Check parameter "Bandwidth B1" (P2.1)
[
Automatic voltage regulation not
functioning.
▪ The on-load tap-changer is in
the end position.
▪ Travel commands for regulat-
ing the measured voltage are
in the wrong direction.
Function "Invert travel commands
(F5)" is set incorrectly.
Check "Invert travel commands (F5)" function
[
Automatic voltage regulation is
blocked.
▪
LED is lit.
▪ The display does not show an
event code.
Blocking function is activated and
blocking contact (X3) is closed.
Check signal source.
Collective message from
ECOTAP® VPD® CONTROL
PRO.
Check the ECOTAP® VPD® CONTROL PRO.
Automatic voltage regulation is
blocked.
▪
LED is lit.
▪ The display shows an event
code.
Event code is present.
110].
Automatic voltage regulation is
blocked.
Voltage blocking is active.