7 Operation
Maschinenfabrik Reinhausen GmbH 2021
80
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
7.4.2 Voltage blocking (P4)
You can use voltage blocking to define limit values for blocking the auto-
matic voltage regulation (AVR AUTO). This allows you to avoid unnecessary
tap-change operations in the event of strong voltage changes in the mains.
▪ Undervoltage blocking: Blocking is activated as soon as the measured
value is less than the limit value.
▪ Overvoltage blocking: Blocking is activated as soon as the measured
value is greater than the limit value.
7.4.2.1 Undervoltage blocking (P4.1)
To set the undervoltage blocking, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
ð
3. Press
to confirm the selection.
4. Press
or
to select the desired value. Alternative: Press
+
or
+
to set the value in larger steps.
5. Press
to confirm the selection.
6. Press
to save the setting.
7.4.2.2 Overvoltage blocking (P4.2)
To set the overvoltage blocking, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
3. Press
until the desired parameter is displayed.
ð
4. Press
to confirm the selection.
5. Press
or
to select the desired value. Alternative: Press
+
or
+
to set the value in larger steps.