6 Commissioning
Maschinenfabrik Reinhausen GmbH 2021
54
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
The
LED can remain lit for up to 30 minutes after the voltage supply is
disconnected. This indicates that the energy accumulator is still charged.
This does not represent a hazard during mounting or removing the control
unit.
1. Coil the connection cable and secure it on the motor-drive unit.
2.
NOTICE!
Damage to the control unit. Ensure that the control unit is fully
disconnected.
3. Carry out dielectric tests on the transformer wiring.
4. Connect the connectors to the terminals X4, X2 and X1 on the control
unit.
6.1.3 Resetting automatic adjustment
Reset the automatic adjustment prior to transporting the transformer to the
installation site. This ensures that automatic adjustment is carried out again
during commissioning at the installation site.
To reset the automatic adjustment, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
.
2. Press
+
for longer than 5 seconds.
ð
3. Press
until code 3 is displayed.
ð
4. Press
to confirm the selection.
ð
The LED
lights up and event code E4 is displayed.