2. Clean sealing surfaces on sealing module and underside of transformer
cover. Insert O-ring supplied in sealing module.
Figure 4: O-ring
3.
NOTICE!
Damage to the on-load tap-changer due to incorrect screw con-
nections. Guide the on-load tap-changer from below through the opening
in the transformer cover and affix horizontally to the transformer cover us-
ing 4 screws. Evenly tighten screws crosswise by hand.
4. Tighten the screws crosswise with 9 Nm. Ensure that the fastenings are
not subject to mechanical stress.
5. Check the fit of the flange and O-ring for evenness.