5.6 Drying the on-load tap-changer
NOTICE
Damage to the on-load tap-changer, motor-drive unit and con-
trol unit.
If temperature-sensitive components are dried, they may become damaged.
► Remove motor-drive unit and control unit and do not dry.
► Affix the transport locking plate prior to drying to protect the on-load tap-
changer.
► Ensure that the temperature of the on-load tap-changer does not exceed
135°C.
Removing motor-drive unit and control unit
1.
DANGER!
Risk of fatal injury due to electrical voltage. Ensure that all
cables in the working area are de-energized and that the shutdown equip-
ment is locked so that it cannot be switched on again.
2. Remove connectors from the terminals X1, X2 and X4 on the control unit.
Figure 27: Disconnecting the connection cable
3. Coil the connection cable and secure it on the motor-drive unit.