7 Operation
Maschinenfabrik Reinhausen GmbH 2021
84
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
5. Press
to save the setting.
7.4.6 Regulating range (P8)
You can limit the permissible regulating range as necessary. Here, you can
set the lowest operating position and the highest operating position.
The limited regulating range applies to all operating modes. You can, how-
ever, move to an operating position outside of the permissible regulating
range via the "Target position for loss of voltage" function.
7.4.6.1 Lowest operating position (P8.1)
You can use this parameter to set the lowest permissible operating position.
To do so, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
3. Press
until the desired parameter is displayed.
ð
4. Press
to confirm the selection.
5. Press
or
to select the desired value.
6. Press
to confirm the selection.
7. Press
to save the setting.
7.4.6.2 Highest operating position (P8.2)
You can use this parameter to set the highest permissible operating position.
To do so, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
3. Press
until the desired parameter is displayed.
ð
Содержание ECOTAP VPD 3 30D-24
Страница 131: ......