By340_04b_oi_e.doc / Apr-16
Page 31 / 42
8.2.9.
Special functions
F08
Range
Default
F08.064 Digital input filter: must be set to “0”.
0 … 3
0
F08.065 Trigger threshold for encoder1 inputs *)
30 … 250
166
F08.066 Trigger threshold for encoder2 inputs *)
30 … 250
166
F08.067 Brightness of the 7-segment LED display
0 … 4
0
0= 100% of maximum brightness
1= 80% of maximum brightness
2= 60% of maximum brightness
3= 40% of maximum brightness
4= 20% of maximum brightness
F08.068 Frequency Control: must be set to “0”
0 … 1
0
F08.069 Factor Storage
0 … 1
0
0= Factor temporary active until next power-down **)
1= Factor stored to EEProm for enduring use **)
F08.070 Display Time: Update time (sec.) for display only
0.005 … 9.999
0.050
F08.071 Default Display: Number of actual value displayed by
the unit after power up (see table in chapter
9.1
at
description of Scroll Display command)
0 … 8
0
*) Must be set to the default value (166) for any kind of input signals, except for single-
ended TTL signals which require a setting of 35.
**) Refers only to those changes of the speed ratio settings where either the “Direct Fast
Access” menu (see chapter
7.3
) or the motor potentiometer function (operation mode 4,
see chapter
6
) have been used.
8.2.10.
Keypad protection codes
F09
Range
Default
F09.071 Protected group F01
F09.072 Protected group F02
0
F09.073 Protected group F03
0 = no protection
F09.074 Protected group F04
F09.075 Protected group F05
1 – 999 999 =
F09.076 Protected group F06
Protection code
F09.077 Protected group F07
for the actual
F09.078 Protected group F08
parameter group
F09.079 Protected group F09