By340_04b_oi_e.doc / Apr-16
Page 16 / 42
The adjoining sequence of key operations explains how to change
Parameter number 052 of group F06 from the original value of 0 to a new value of 8:
Step
State
Key action
Display
Comment
00
Normal operation
Actual Error
01
> 2 sec.
F01
Display of the
Parameter group
02
Level:
Parameter group
5 x
F02 … F06
Select group # F06
03
F06.050
Confirmation of F06.
The first parameter of this
group is F06.050
04
Level:
Parameter numbers
2 x
F06.051…
F06.052
Select parameter 052
05
0
Parameter 052 appears in
display, actual setting is 0
06
Level:
Parameter values
8 x
1 …. 8
Setting has been modified
from 0 to 8
07
F06.052
Save the new setting (8)
08
Level:
Parameter numbers
F06
Return to level parameter
groups
09
Level:
Parameter groups
Actual Error
Return to normal operation
10
Normal operation
During the general setup procedure all control activities remain disabled.
New parameter settings become active after return to normal operation only.
7.3.
Direct Fast Access to Speed Ratio Setting
To get to the fast access routine, please press both
and
at the same time
This will access the parameter group F01 right away. To change the settings follow the same
procedure as already described above. Besides the advantage of direct access, the fundamental
difference to general setup is the following:
During the fast access procedure all control functions remain fully active.
Access is limited to Factor settings; no other parameters can be changed.