9.3.
Display of Actual Values
During normal operation it is possible to display an actual value. Two LEDs at the front panel
indicate the actual value displayed. You can scroll the actual value on the display by Scroll
Display command, which can be assigned either to a key or to an input. Parameter F08.071
“Default Display” selects the actual value to be displayed after power up of the unit.
No. Display
L1 (red)
L2 (yellow)
0 Display OFF (only two decimal points are lit to indicate
operation state)
OFF
OFF
1 Position error (differential counter)
OFF
OFF
2 Position error (bar graph display, see diagram below)
OFF
OFF
3 Actual Master speed
The speed display can be scaled by the two parameters
F03.029 Speed Display Factor and F03.030 Speed:
030
.
03
029
.
03
]
[
F
F
Hz
frequency
Master
value
Display
If you want to display a decimal point with the speed
value you can select the position of the decimal point by
parameter F03.031 Speed Display Dec.Point.
ON
OFF
4 Recorded Minimum Error since last “Clear min-max”
command
OFF
ON
5 Recorded Maximum Error since last “Clear min-max”
command
ON
ON
6 Pulse count between two Master index pulses
Flashing
OFF
7 Pulse count between two Slave index pulses
OFF
Flashing
8 Index position error (
Flashing
Flashing
Slave lags Master
Slave leads Master
-4 ... 0 ... +4
+5 ... +8
+9 ... +16
+17 ... +32
+33 ... +64
> +64
Bar graph display with reference to the actual synchronization error
The diagram shows positive errors only (Slave lags Master). Negative errors are mirror-inverted
.