By340_04b_oi_e.doc / Apr-16
Page 36 / 42
Set all parameters in the Edit filed according to your needs, following the hints given in this
manual. The following parameters should initially be set to the values as shown:
Number Register
Initial Setting
F02.004 Operation mode
1
F02.006 Integration Time
0000
F02.007 Correction Divider
0
F05.040 Correction Gain
1.000
F05.041 Max. Correction
10.000
After entry of all parameters click to “Transmit All” followed by “Store EEProm” to store all
parameters to the BY340 or BY641 controller.
At this time, both drives (Master and Slave) must be adjusted to proper and stable
operation over the full speed range. Slave drive settings must provide a maximum
of dynamics and response (set ramps to zero, switch of any integral or differential
component of the internal speed control loop, operate the drive with proportional
speed control only, with the proportional Gain set as high as possible).
10.1.
Running the Adjust menu
For adjustments of directions and control gains of the slave drive, you need to open the
„Adjust“ menu available under „Tools“ in the main menu of the screen. To start the Adjust
menu the first time, the Slave drive should be disabled for reasons of safety.