By340_04b_oi_e.doc / Apr-16
Page 22 / 42
F02
Range
Default
F02.007
Correction Divider:
Function to provide a digital attenuation of the
phase correction signal that is produced, when the
drive on mechanical grounds (dead band or
backlash) cannot respond. In such a case, it is not
desirable to make corrections immediately. The
"Correction Divider" provides a window for the
drive "backlash", within which the controller
produces no correction and a division of the
differential error count.
0 = No window, Reaction to 1 increment, no
division
1 = /- 1 increments, error division by 2
2 = /- 2 increments, error division by 4
3 = /- 4 increments, error division by 8
etc.
0 … 9
0
F02.008
Factor 1 Scaling:
This factor allows scaling of the remote Factor 1
entry to "user units" or to adapt the numeric value
of Factor 1 to the application.
0.00001 ... 9.99999 1.00000
It is essential, for all steps of set-up, to program F1-Scaling Factor to 1.00000 first in order to
avoid confusions with factor calculations. This ensures that the Factor setting corresponds to the
real operative Factor 1.
Once the set-up procedure is terminated, set F1-Scaling Factor to the numeric value that later
should correspond to an operative value of 1.0000 for Factor 1.
Example: If the operator desires to set 3.50000 instead of 1.00000, set F1-Scaling Factor to
3.50000. For all factor calculations, please be aware if you operate with a proportional or a
reciprocal characteristic of Factor1!
F02.009
F02.010
Factor 1 Minimum:
Factor 1 Maximum:
These are limitations of the setting range of Factor
1 and out of range settings will be overwritten by
the appropriate min or max value.
With Factor 1 Minimum set to 0.95000 and Factor 1
Maximum set to 1.05000, the operator is limited to
a +/- 5% variation of the speed ratio.
0.00001 ... 9.99999 0.00001
9.99999