Part Number: 000016427 Rev 00 08/2020 87
Use the following procedure and table to help determine if a harvest valve is remaining
partially open during the freeze cycle.
1. Wait five minutes into the freeze cycle.
2. Feel the inlet of the harvest valve.
Important
Feeling the harvest valve outlet or across the harvest valve itself will not work for this
comparison.
The harvest valve outlet is on the suction side (cool refrigerant). It may be cool enough
to touch even if the valve is leaking.
3. Feel the compressor discharge line.
n
Warning
The inlet of the harvest valve and the compressor discharge line could be hot enough to
burn your hand. Just touch them momentarily.
4. Compare the temperature of the inlet of the harvest valve to the temperature of the
compressor discharge line.