68
Testing and Troubleshooting
Problem:
Cannot connect to the controller via Ethernet
Solution:
See the Morningstar Product Connectivity Manual, available on our website:
http://www.morningstarcorp.com/wp-content/uploads/2014/02/MS-Comm-Document-2010.pdf
GFPD-600V
Test Button Uses:
The test button can be used for three purposes:
1. With the GFPD-600V in normal mode, pressing the test button conducts a system test that opens
the breaker, shows a red solid LED, and sounds the buzzer;
2. When a ground-fault error has occurred, pressing the test button resets the GFPD-600V to the
normal
condition;
3. When a wiring error / open breaker alarm has occurred, pressing the test button resets the
GFPD-600V to the normal condition.
Faults and Corrections:
♦ When a ground-fault error has occurred, push the test button and then close the breaker to
resume normal operation. Have a qualified technician investigate the ground-fault cause.
♦ When a wiring error / open breaker alarm has occurred, correct wiring error and/or close breaker.
Push the test button to resume normal operation.
♦
When the low battery voltage threshold of nine volts is reached, the buzzer will sound. To
resume normal operation, re-charge or replace the battery powering the GFPD-600V.
♦
Push the test button to perform a system test. Close the breaker to resume normal operation.
♦
A critical fault indicates a hardware malfunction. Please contact Morningstar for instructions.
♦
If previous trouble-shooting does not correct the problem, re-start the unit by removing in-line
source fuse, and re-installing.
69
TriStar MPPT 600V-TR Operator’s Manual
Your TS-MPPT-600V-TR will provide years of reliable and trouble-free service. The unit contains
no electromechanical parts such as relays or cooling fans that can wear out and fail. Additionally,
there are no user-serviceable parts inside the controller.
7.1 Important Safety Instructions
SAVE THESE INSTRUCTIONS.
This manual contains important safety, installation and operating instructions for the
TS-MPPT-600V-TR solar controller. The following symbols are used throughout this manual to
indicate potentially dangerous conditions or mark important safety instructions:
WARNING:
Indicates a potentially dangerous condition. Use extreme caution
when performing this task.
!
CAUTION:
Indicates a critical procedure for safe and proper operation of the
controller.
NOTE:
Indicates a procedure or function that is important for the safe and
proper operation of the controller.
AVERTISSEMENT :
Indique une condition potentiellement dangereuse. Faites preuve
d’une prudence extrême lors de la réalisation de cette tâche.
!
PRUDENCE :
Indique une procédure critique pour l’utilisation sûre et correcte du
contrôleur.
REMARQUE :
Indique une procédure ou fonction importante pour l’utilisation sûre et
correcte du contrôleur.
Safety Information
• Read all of the instructions and cautions in the manual before beginning installation.
• There are no user serviceable parts inside the TS-MPPT-600V-TR. Do not disassemble
or attempt to repair the controller.
WARNING:
RISK OF ELECTRICAL SHOCK.
NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM
DC INPUT, AND MAY BE ENERGIZED WITH HAZARDOUS SOLAR VOLTAGE. UNDER CER-
TAIN FAULT CONDITIONS, BATTERY COULD BECOME OVER-CHARGED. TEST BETWEEN
ALL TERMINALS AND GROUND BEFORE TOUCHING.
Maintenance and Service
7.0