5.4.3.4 Enable or Disable Delayed Day Modes
•
The Delayed Day Mode operation is configured at Level 3 by the installer / maintenance contractor.
•
For example, the Delayed Day Mode may be set to be active between 8:00 and 17:00. Outside of these
hours, a fire alarm condition will immediately sound the bells and activate outputs.
•
The Delayed Day Mode causes the panel to respond to high sensor signals by sounding the panel buzzer
and displaying a warning message on the alphanumeric display. The panel delays the activation of the
alarm condition outputs (sounders or relays) for a programmed period.
•
The user may enable or disable the operation of the Delayed Day Mode through the Enable or Disable
Menus.
•
To select Delayed Day Mode, press ‘
4’
from the Enable or Disable Menus. The display now presents two
options:
Disable:
1)Configure the Day Mode Delay Period
2)Temporary Override – Turn Off Delays
Enable:
1)Disable the Day Mode Delay Period
2)Temporary Override – Turn On Delays
5.4.3.4.1 Configure Day Mode Delay Period / Disable Operation
•
To select configure or disable options, press
‘1’
.
•
When enabling the operation of the Delayed Day Mode function, the display prompts for the number of
days the Delayed Day Mode is to be in operation.
Use day mode for the next 2 days OK ?
•
If the prompted number of days is not as required, press the
CHANGE
key and then enter the required
number of days.
•
In the above example, the Delayed Day Mode will be effective for today and tomorrow. The day after
tomorrow, the panel will go immediately into a full fire alarm condition on receiving a high signal from a
device.
•
The number of days can be selected in the range 001 to 199. To permanently enable the Delayed Day
Mode operation, enter the number of days as 200.
•
When Disable Day Mode Delay is selected, the Stage 1 / 2 Day Mode Delay Function is completely turned
off.
5.4.3.4.2 Manual
Override
•
The manual override facility provides a means to override the scheduled time clock for operation of the
stage 1 / 2 Day Mode Delay.
•
If the Turn-On Delays option is selected, the Stage 1 / 2 function will be turned on immediately. It will
automatically turn off again at the end of the next scheduled time.
•
If the Turn-Off Delays option is selected, the Stage 1 / 2 function will be immediately turned off. It will
automatically turn on at the start of the next scheduled time.