Enter the address of the device required. If the address is less than 3-digits long (for example address
34), this can be entered as either
034
or
34
followed by
ENTER
.
•
The display will then ask for confirmation (OK?).
Loop 2 Address 34 OK ?
•
Press the
Yes
key to confirm.
•
When an individual point is disabled, the DISABLEMENT LED will be illuminated.
•
The corresponding Zone FAULT LED will only be illuminated if all devices in the zone are disabled.
Networked Panels
•
Master panels are able to command other panels to enable or disable individual devices.
•
In this case, the display will prompt with an additional, opening question requesting the panel (CPU)
number.
CPU __
•
Enter the address of the required panel. The display will then prompt for the loop and device address
information as described above.
5.4.3.3 Enable or Disable Keys
•
To disable the panel control keys, press
‘3’
from the disable menu.
•
The user Level 2 password will then be required to re-enable the panel control keys and provide access to
the User Option Functions.
The panel keys will be automatically disabled if a key has not been pressed for a pre-
programmed period.