ZX2E/ZX5E Fire Alarm Control Panels
Page 14 of 28
Document No. 996-130, Revision: 01,
User Manual
5.4.1 Test
•
To display the Test Menu, press
‘2’
and the display shows:
1)LEDs 2)LCD 3)Zones 4)Outputs
5)Audible Indicator
•
The test menu allows the user to test:
1. The LED’s on the front panel display.
2. The alphanumeric (liquid crystal) display.
3. The detection and alarm initiating devices connected to the signaling loop.
4. The sounder outputs and other alarm condition output devices connected to the system.
5. The internal buzzer.
5.4.1.1 LED
Test
•
To select the option, press
‘1’
.
•
To terminate the test, press
No
.
•
The panel will flash all of the indicators on the LED Display and will step through all of the Zone FIRE and
FAULT indicators.
5.4.1.2 LCD
Test
•
To select the option, press
‘2’
.
•
To terminate the test, press
No
.
•
The alphanumeric display will flash all displayable characters in all positions of the display and then return
to the menu.
5.4.1.3 Zones
Test
5.4.1.3.1 Configuring the Test
•
The ‘Walk Test’ option allows the user to conveniently test the detection and alarm initiating devices
without having to continually reset the panel.
•
To select the option, press
‘3’
.
If no action is taken at this point, the display will automatically revert to the normal display
after 1 minute. Pressing SHIFT or > will return the display to the test display.
•
The display will then prompt for whether the sounder outputs should ring:
Ring Bells?
•
Press
Yes
and the sounders (dependent on their programming) will ring for a few seconds and then be
reset automatically when a device is tested. (NOTE: Relay Outputs are never activated).
•
Press
No
and the sounders will not ring.
•
The panel can be set to test a range of zones. The display will prompt for the first zone to be tested: