MORLEY-IAS
ZX2E/ZX5E Fire Alarm Control Panels
Page 18 of 28
Document No. 996-130, Revision: 01,
User Manual
5.4.3.1 Enable or Disable Zones
•
To enable or disable input devices by zone, select option 1.
Any loop driven output devices such as sounders or relay modules will still activate as
programmed even if disabled. Only the input signal from these devices will be ignored.
•
Press
‘1’
and the display will prompt for the required zone number.
Disable Zone ?
( Enter number or use “>” to scroll )
•
Key in the zone number and then press the
ENTER
key. Or use the > key to scroll through the zones.
Disable Zone 14 OK ?
•
The display will then repeat the zone number and ask for confirmation (OK?). Press the
YES
key to
confirm.
•
The panel will enable or disable all of the input devices in the zone including smoke, temperature and call
points.
•
When a zone is disabled, the DISABLEMENT LED and the corresponding yellow Zone FAULT LED will
be illuminated.
(NOTE: If the panel is installed and programmed to operate in accordance with BS5839 then disabling a
zone does NOT disable call points within that zone).
5.4.3.2 Enable or Disable Inputs
•
To enable or disable individual input devices, select option 2.
Any loop driven output devices such as sounders or relay modules will still activate as
programmed even if disabled. Only the input signal from these devices will be ignored.
•
Press
‘2’
and the display will prompt for the signalling loop circuit number where the device is located.
Loop _
•
Enter the required loop number (1 for ZX1E, 1-2 for ZX2E or 1-5 for ZX5E) and the display will prompt for
the numeric address of the device:
Loop 2 Address ____