5.4.1.3.3 Inspecting Other Conditions During a Walk Test
EN54
9
EN54-2 5.1
Display of
functional
conditions:
•
To inspect Fire, Fault or Disablement Conditions whilst a walk test is in
progress, press the
‘>’
key.
•
This returns the display to the menu options from which all other operating conditions can be inspected.
•
To cancel the walk test, re-select the Zones Test Option. The display will then return to the normal walk
test view, showing the current walk test in operation. For example:
Test from zone 12 to zone 15
-----W-------------------------------------
•
Then press the
‘NO’
key to cancel the test.
5.4.1.4 Output
Test
Access to this test option is only available to users with the Level 3 password.
•
To select the option, press
‘4’
and then enter the password
‘####’
.
•
To terminate the test, press
No
.
•
The output test allows the relays and sounders to be individually operated. The first six outputs are
reserved for the panel’s own onboard relay and sounder circuits as shown below:
Output 1 – Onboard Relay 1
Output 2 – Onboard Relay 2
Output 3 – Onboard Sounder A
Output 4 – Onboard Sounder B
Output 5 – Onboard Sounder C
(Only available on ZX5E panel!)
Output 6 – Onboard Sounder D
(Only available on ZX5E panel!)
•
On entering the test, the display will show the current state of the first output:
RELAY OPERATED
1
•
To advance to the next output, press the
>
or the
YES
key.
RELAY NOT OPERATED
2
•
To change the output state, press the
CHANGE
key. The display will show the new state: