ZX2E/ZX5E Fire Alarm Control Panels 

 

MORLEY-IAS 

 

User Manual 

Document No. 996-130, Revision: 01,  

Page 11 of 28 

5  Level 2 Control Functions 

 

• 

All of the functions and operational features described for Level 1 user are available and are the same for 
a Level 2 user. 

• 

To enable Level 2 operation, press the SHIFT key. The display will then show: 

 

[Panel ACTIVE Control Keys INHIBITED]   [1] 

Do you want to enable the control keys? 

 

• 

Press the 

YES

 key and the display will prompt for entry of the password. 

 

[Panel ACTIVE Control Keys INHIBITED]   [1] 

Please Enter Password 

 

• 

Enter the 

4-digit Level 2 password

. The display then shows the Main Menu of user options. 

 

[ACTIVE]  1)Commission 2)Test  3)Time   [1] 

4)Enable  5)Disable    6)Print 7)View 

 
 

• 

If a key has not been pressed for a certain period, the display will revert to the normal Level 1 display 
showing the system status message. To re-show the menu display, press the 

SHIFT

 key. 

• 

If a key has not been pressed for a specified period of time, (normally 5 minutes – programmable), then 
‘Level 2’ access will be automatically cancelled. It will be necessary to re-enter the password to re-activate 
Level 2 functions. 

5.1  Power Failure Condition 

5.1.1  AC Mains Power Failure Indication 

• 

If the AC MAINS input is interrupted, the AC Power LED will flash and the panel buzzer will sound. 

• 

The back light illumination of the alphanumeric display will be turned off, the alphanumeric display will 
show an ‘AC Fail’ message and the Supply Fault LED Indicator will be lit. 

• 

If both the AC MAINS input and the Battery Standby Input fail then all LED and alphanumeric display 
indicators will be off. 

• 

To silence the panel buzzer, press the 

MUTE BUZZER

 key. 

• 

When the AC MAINS is restored, the AC Power LED returns to steady on. 

• 

To clear the latched AC MAINS Fault, press the 

SYSTEM RESET

 key. 

• 

When MUTED, the buzzer will continue to sound a short beep every 30 seconds. This gives an on-going 
warning of the continued AC Mains Failure condition. 

5.1.2  Battery Low / Charger Failure 

• 

If the battery becomes disconnected or the battery voltage is less than 21V DC or if there is a failure in the 
circuitry that charges the battery, then the panel shows a ‘Battery Low / Charger Failure’ message. 

• 

To silence the panel buzzer, press the 

MUTE BUZZER

 key. 

• 

To clear the latched Fault, press the 

SYSTEM RESET

 key.  If the fault is still present it will be redisplayed. 

 

Содержание ZX1e

Страница 1: ...ZX1e ZX2e Document No 996 130 Issue 01 user manual ZX5e...

Страница 2: ...ns Power Failure Indication 11 5 1 2 Battery Low Charger Failure 11 5 2 FAULT CONDITIONS 12 5 2 1 Fault Indication 12 5 2 2 User Actions 12 5 3 FIRE ALARM CONDITIONS 12 5 3 1 Fire Alarm Indications 12...

Страница 3: ...s FIGURE 1 ZX1E ZX2E CONTROLS AND DISPLAYS 6 FIGURE 2 ZX5E CONTROLS AND DISPLAYS 6 FIGURE 3 SYSTEM CONTROL LED DISPLAY 7 Table of Tables TABLE 1 CONTROL KEY FUNCTIONS 6 TABLE 2 ALPHANUMERIC AND INTERA...

Страница 4: ...ire Alarm Control Panels are 1 1 2 and 1 5 loop panels for use with analogue addressable devices from the following detector manufacturer ranges Apollo S90 Hochiki Morley IAS Nittan System Sensor 1 2...

Страница 5: ...dicate the location of any fire alarm or fault and the alphanumeric display gives more detailed fire alarm or fault information At USER LEVEL 1 all the displays are functional but the front panel cont...

Страница 6: ...6 2 63 64 65 6 6 6 7 6 8 69 7 0 71 72 73 7 4 75 7 6 7 7 78 79 80 Figure 1 ZX1E ZX2E Controls and Displays Figure 2 ZX5E Controls and Displays Key Legend Symbol Function Sound Alarms Press to Turn on A...

Страница 7: ...s are disabled at USER LEVEL 1 Pressing the SHIFT key will cause the display to prompt for entry of the Level 2 password The password must be entered to re enable the control keys at Level 2 3 2 Front...

Страница 8: ...nder outputs and the delays are active in force The delays may be enabled or disabled Refer to Disablement Function Relays Disabled Yellow The relay outputs have been disabled Refer to Disablement Fun...

Страница 9: ...anel If there are no alarm or fault conditions the display will show the date and time Pressing the SHIFT key will show a list of optional functions or prompt for the level 2 password Panel ACTIVE Con...

Страница 10: ...alphanumeric display indicators will be off 4 3 Fire Alarm Conditions If the control panel initiates an alarm condition the FIRE LED Indicators will be illuminated and if appropriate the relevant ZON...

Страница 11: ...re enter the password to re activate Level 2 functions 5 1 Power Failure Condition 5 1 1 AC Mains Power Failure Indication If the AC MAINS input is interrupted the AC Power LED will flash and the pane...

Страница 12: ...al mode 5 3 Fire Alarm Conditions The panel will indicate a fire alarm condition if it detects an alarm condition or if the SOUND ALARMS key is pressed 5 3 1 Fire Alarm Indications If the control pane...

Страница 13: ...ystem The following tests can be performed LED To test the LED indicator lamps This test will automatically test each zone indicator and then terminate LCD To test the alphanumeric display ZONES To pe...

Страница 14: ...press 2 To terminate the test press No The alphanumeric display will flash all displayable characters in all positions of the display and then return to the menu 5 4 1 3 Zones Test 5 4 1 3 1 Configuri...

Страница 15: ...the alphanumeric display write the event in the event log sound the panel buzzer and illuminate the appropriate zone FIRE LED 2 Turn on the LED at the sensor that initiated the alarm 3 After a few sec...

Страница 16: ...test 5 4 1 4 Output Test Access to this test option is only available to users with the Level 3 password To select the option press 4 and then enter the password To terminate the test press No The ou...

Страница 17: ...time to that of the master panel when a reset is performed on the master panel 5 4 3 Enable Disable Functions To select the enable or disable menu options press 4 or press 5 as required from the user...

Страница 18: ...el will enable or disable all of the input devices in the zone including smoke temperature and call points When a zone is disabled the DISABLEMENT LED and the corresponding yellow Zone FAULT LED will...

Страница 19: ...vices in the zone are disabled Networked Panels Master panels are able to command other panels to enable or disable individual devices In this case the display will prompt with an additional opening q...

Страница 20: ...isable Operation To select configure or disable options press 1 When enabling the operation of the Delayed Day Mode function the display prompts for the number of days the Delayed Day Mode is to be in...

Страница 21: ...ning message will also be shown on the alphanumeric display The sounders can only be disabled after confirmation by re entering the Level 2 password 5 4 3 6 Enable or Disable Delays If the panel has b...

Страница 22: ...s follows 1 Devices Prints out the present status and text assigned to all devices on a loop 2 Events Prints out the contents of the event log 3 Mode Sets the printing mode The current mode of operati...

Страница 23: ...r keys 3 Faults Displays the current panel fault status The display is identical to the automatic fault fire alarm display but with the ability to manually scroll through all the faults using the and...

Страница 24: ...g delayed day mode the internal buzzer will sound The sensor location will be shown on the display along with a warning that the panel has entered stage 1 of a delayed alarm If the warning is not ackn...

Страница 25: ...rded All events should be properly recorded events include real and false fire alarms faults pre alarm warnings tests temporary disconnection s and service visits A brief note of any work carried out...

Страница 26: ...IAS ZX2E ZX5E Fire Alarm Control Panels Page 26 of 28 Document No 996 130 Revision 01 User Manual EVENT DATA Date Time Counter Reading Event Action Required Date Completed Initials Table 7 Logbook Eve...

Страница 27: ...ZX2E ZX5E Fire Alarm Control Panels MORLEY IAS User Manual Document No 996 130 Revision 01 Page 27 of 28 NOTES...

Страница 28: ...Page 28 of 28 Document No 996 130 Revision 01 User Manual MORLEY IAS All rights reserved The MORLEY IAS Logo is a registered trademark MORLEY IAS Fire Systems Charles Avenue Burgess Hill West Sussex...

Отзывы: