background image

TDY

 

Demand Moore Reliability 

7

RTD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T/C 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 2.

  Input Types, Ranges, Minimum Span and Maximum Range Specifications, and Accuracy of the TDY

0.003750 

 

 

0.003850 

 

 

0.003902

 

 

 

0.003911 

 

 

0.003916 

 

 

0.003923

 

 

 

0.003926

 

 

 

0.003928

 

 

 

0.000672

 

 

 

0.000427

 

 

 

n/a 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

100, 200, 300,  

 

400, 500, 1000

 

 

100, 200, 400

 

500, 1000

 

 

100, 500

 

 

 

100 

 

 

98.129

 

 

 

100, 470, 

 

500 

 

100 

 

 

120

 

 

 

9.035 

 

 

n/a 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

n/a 

 

 

-100 to 560°C

 

-148 to 1040°F

 

 

-240 to 960°C

 

-400 to 1760°F

 

 

-150 to 720°C

 

-238 to 1328°F

 

 

-235 to 710°C

 

-391 to 1310°F

 

 

-240 to 580°C

 

-400 to 1076°F

 

 

-235 to 680°C

 

-391 to 1256°F

 

 

-235 to 710°C

 

-391 to 1310°F

 

 

-260 to 962°C

 

-436 to 1763.6°F

 

 

-100 to 360°C

 

-148 to 680°F

 

 

-65 to 280°C

 

-85 to 536°F

 

 

n/a 

 

-210 to 770°C

 

-346 to 1418°F

 

 

-270 to 1390°C

 

-454 to 2534°F

 

 

-270 to 1013°C

 

-454 to 1855.4°F

 

 

-270 to 407°C

 

-454 to 764.6°F

 

 

-50 to 1786°C

 

-58 to 3246.8°F

 

 

-50 to 1786°C

 

-58 to 3246.8°F

 

 

200 to 1836°C

 

392 to 3336.8°F

 

 

-270 to 1316°C

 

-454 to 2400.8°F

 

 

0 to 2338°C

 

32 to 4240.4°F

Direct resistance  
or Potentiometer

 

 

J

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-50 to 500°C

 

-58 to 932°F

 

 

-200 to 850°C

 

-328 to 1562°F

 

 

-100 to 650°C

 

-148 to 1202°F

 

 

-200 to 630°C

 

-328 to 1166°F

 

 

-200 to 510°C

 

-328 to 950°F

 

 

-200 to 600°C

 

-328 to 1112°F

 

 

-200 to 630°C

 

-328 to 1166°F

 

 

-200 to 850°C

 

-328 to 1562°F

 

 

-80 to 320°C

 

-112 to 608°F

 

 

-50 to 250°C

 

-58 to 482°F

 

 

0-4000

 

 

-180 to 770°C

 

-292 to 1418°F

 

 

-150 to 1372°C

 

-238 to 2501.6°F

 

 

-170 to 1000°C

 

-274 to 1832°F

 

 

-200 to 400°C

 

-328 to 752°F

 

 

0 to 1768°C

 

32 to 3214.4°F

 

 

0 to 1768°C

 

32 to 3214.4°F

 

 

400 to 1820°C

 

752 to 3308°F

 

 

-130 to 1300°C

 

-202 to 2372°F

 

 

0 to 2315°C

 

32 to 4199°F

Input 

      Type 

         α

 

    

Ohms

   Conformance 

   Range

  Minimum 

   Span

 Input Accuracy

  Maximum 

   Range

 

 

 

 

 

 

 

 

15°C (27°F) for

 

100

 inputs 

 

10°C (18°F) for

 

200

 inputs 

 

7.5°C (13.5°F) 

for 500 and 

1000

 inputs 

 

 

 

 

 

 

 

10°C (18°F)

 

 

 

100°C (180°F)

 

 

 

30

 

 

35°C

 

63°F

 

 

40°C

 

72°F

 

 

35°C

 

63°F

 

 

20°C

 

36°F

 

 

50°C

 

90°F

 

 

50°C

 

90°F

 

 

75°C

 

135°F

 

 

45°C

 

81°F

 

 

100°C

 

180°F

 

±0.11°C 

±0.2°F

 

 

 

±0.21°C 

±0.38°F

 

 

 

±0.15°C 

±0.27°F

 

 

 

±0.17°C 

±0.31°F

 

 

 

±0.14°C 

±0.25°F

 

 

 

±0.16°C 

±0.29°F

 

 

 

±0.17°C 

±0.31°F

 

 

 

±0.21°C 

±0.38°F

 

 

 

±0.16°C 

±0.29°F

 

 

 

±1.2°C 

±2.16°F

 

 

 

±0.4

Ω    

− 

 

 

±0.28°C 

±0.5°F

 

 

 

±0.3°C 

±0.54°F

 

 

 

±0.26°C 

±0.47°F

 

 

 

±0.24°C 

±0.43°F

 

 

 

±0.71°C 

±1.28°F

 

 

 

±0.71°C 

±1.28°F

 

 

 

±0.43°C 

±0.77°F

 

 

 

±1.33°C 

±2.39°F

 

 

 

±1.16°C 

±2.09°F

α

 values with both 32 and 128-point linearization curves are available. (lower resolution values provided for compatibility with older units.)

 Ohms

Millivolts  

  DC  

  

n/a 

             n/a 

  -50 to 1000mV 

        4mV                      ±0.04mV 

   -50 to 1000mV    

Platinum 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nickel 

 

 

Copper 

1000

Содержание TDY

Страница 1: ...a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual TDY PC Programmable Temperature Transmitter with Display No 235 740 00J M...

Страница 2: ...Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 2816 E mail info miinet com TOLL FREE 1 800 999 2900 www miinet com 1 Lloyds Court Manor...

Страница 3: ...re 10 Gathering the Equipment Needed 10 11 PC Configuration Software Summary 12 Keeping What You ve Got Safe Using the Get Setup Function 13 Selecting Input Type Wiring etc 14 Scaling the Input also S...

Страница 4: ...Connected TDY 23 Installing and Connecting the TDY 24 Connecting the TDY in an Application 24 Recommended Ground Wiring Practices 24 CE Conformity 24 Dimensions 25 26 Installation in Hazardous Locatio...

Страница 5: ...by user designation inversely proportional to the input Available in your choice of explosion proof or NEMA 4X enclosures the TDY has certified protection in even the toughest environments Combine th...

Страница 6: ...isplay is always two decimal places Range 99999 to 99999 Minimum Display Span 1 00 Operating and Storage Range Transmitter 40 C to 85 C 40 F to 185 F Display 20 C to 65 C 4 F to 149 F Relative Humidit...

Страница 7: ...o 650 C 148 to 1202 F 200 to 630 C 328 to 1166 F 200 to 510 C 328 to 950 F 200 to 600 C 328 to 1112 F 200 to 630 C 328 to 1166 F 200 to 850 C 328 to 1562 F 80 to 320 C 112 to 608 F 50 to 250 C 58 to 4...

Страница 8: ...explosion proof enclosure with two inch entry ports and a glass cover BH2TG 2 Hub explosion proof enclosure with two inch entry ports and a glass cover BH2MG 2 Hub explosion proof enclosure with two M...

Страница 9: ...TDY Configuration Program on a PC Once the program is loaded and running nearly all of the operating parameters for the connected transmitter are shown on a single screen see Figure 3 This makes it ea...

Страница 10: ...verything is setup as shown in Figure 2 and it is not possible to store a tag name in the memory of a transmitter without connecting that transmitter to the Configuration Program Table 3 lists the thi...

Страница 11: ...Y COMM CABLE 803 040 26 FOR NON ISOLATED 803 039 26 FOR ISOLATED 804 030 26 FOR USB Thermocouple Millivolts Inputs 2 Wire RTD Direct Resistance Inputs 3 Wire RTD Direct Resistance Inputs 4 Wire RTD Di...

Страница 12: ...Software and will be used often The names and functions of the individual command buttons may change when you press a button 5 Output These scroll bars control the scaling and damping values of the T...

Страница 13: ...am Main Screen To save the Configuration File already resident in the transmitter s memory 1 Start the PC Configuration Program making sure that the TDY is connected as shown in Figure 2 2 Click on th...

Страница 14: ...tton at the bottom center of the screen then on the Prog button This transfers the settings from the software to the memory of the connected transmitter CAUTION Any time a connected TDY is programmed...

Страница 15: ...wnloaded Skip to Step 6 for instructions on getting the settings programmed into TDY nonvolatile memory 5 Select one of these options a Download the current settings into the connected transmitter s m...

Страница 16: ...ay Full The display zero and display full show what values will actually be displayed If the pull down menu in Figure 7 and the radio button on Figure 8 both have Input selected then Display Zero will...

Страница 17: ...Program Screen do not take effect in the unit until the Configuration File is downloaded Skip to Step 5 for instructions on getting the settings programmed into TDY nonvolatile memory 4 Choose from on...

Страница 18: ...it for it to capture the value 8 Click on the button labelled QuiInTrim then the Stop button and finally the Prog button to send the trim values to the transmitter Trimming the Output The TDY has a fu...

Страница 19: ...o this click on the Stop BW Stop Broken Wire Detection button when it is active on the bottom of the screen Setting Miscellaneous Functions Engineering Unit Readout Input Filtering Upscale or Downscal...

Страница 20: ...Main Screen or enter a value directly into the space provided The default damping value is 0 seconds The maximum allowable damping value is 5 056 seconds Using the Loop Test The TDY Loop Test feature...

Страница 21: ...l down menu to set Linearization ON Then click the CustTabl button in the lower left area of the Configuration Main Screen Figure 11 Linearization Must be set to ON to Create a Custom Table 3 Click on...

Страница 22: ...ests filling in the EGU Engineering Units then the number of points and finally the values in the table 9 When the table is complete click on the QuitTabl button and answer Yes on the pop up dialog bo...

Страница 23: ...e File button to bring up the File Management portion of the program 2 Use the Explorer like file display see Figure 13 to locate the file to be retrieved and click on the file to highlight it 3 Click...

Страница 24: ...output signals from Moore Industries productsshouldbewiredusingashielded twisted pair wiring technique Shields should be connected to an earth or safety ground For the best shielding the shield should...

Страница 25: ...Dimensions of the HP housing for the TDY unit 83 8 mm 3 30 in 118 1 mm 4 65 in 130 mm 5 12 in 111 8 mm 4 40 in 82 6 mm 3 25 in 63 5 mm 2 50 in C L Interior Diameter 81 3 mm 3 2 in 134 6 mm 5 30 in In...

Страница 26: ...TDY unit PS PS 1 2 3 4 SDY 16 203 MA 65mm 2 55 in GND 1 2 NPT 102mm 4 00 in 84mm 3 31 in 68mm 2 69 in 129mm 5 06 in 10mm 38 in 53mm 2 09 in 124mm 4 90 in 66mm 2 60 in 25mm 1 00 in 102mm 4 00 in 119mm...

Страница 27: ...lled as Division 2 equipment the TDY shall be mounted within a tool secured enclosure which meets the requirements of ANSI ISA 61010 1or C22 2 No 1010 1 and be capable of accepting the applicable wiri...

Страница 28: ...all be installed in an enclosure which maintains an ingress protection rating of at least IP20 The communications port shall be programmed through Moore Industries Cable Part No 804 030 26 as describe...

Страница 29: ...ale causes this message in the Output section of the Configuration Screen This condition is downloadable to the unit and causes transmitter output to rise proportionally in response to a drop on the i...

Страница 30: ...selves on their ability to provide timely accurate and practical answers to your process instrumentation questions Factory phone numbers are listed on the back cover of this manual If problems involve...

Страница 31: ...ng the intrinsically safe option It also in cludes guidelines for setting up zener barriers neces sary in these types of applications These diagrams must be used to augment the installa tion instructi...

Страница 32: ...TDY 32 Demand Moore Reliability...

Страница 33: ...TDY Demand Moore Reliability 33...

Страница 34: ...y and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...

Отзывы: